Sambygget styreenheder ACP+BA 220..240 V AC

Varenr: | 29470 |
El nr: | 3322294708 |
EAN13 nr: | 3303430294702 |
Pakning: | 1stk |
 |
[Ie] rated operational current | DC-13: 2 A 24 V DC-12: 8 A DC 24 V DC-12: 2 A DC 48 V DC-12: 0.6 A DC 110 V DC-12: 0.4 A DC 250 V AC-15: 5 A AC 48 V AC-15: 5 A AC 24 V AC-15: 4 A AC 110 V AC-15: 3 A AC 220/240 V AC-14: 5 A AC 48 V AC-14: 5 A AC 24 V AC-14: 4 A AC 220/240 V AC-14: 4 A AC |
[Ith] conventional free air thermal current | 8 A |
[Us] rated supply voltage | 220...240 V AC 50/60 Hz |
Accessory / separate part category | Interlocking accessory |
Aflåst udstyr | Compact NS100...630 Compact NS630b...1600 Masterpact NT Masterpact NW NSX100...250 NSX400...630 |
Driftsforløb | Automatisk operation Forced operation on normal source Forced operation on replacement source Stop (both normal and replacement source off) |
Enhedens korte navn | ACP + BA |
IK kapslingsklasse | Front: IK07 conforming to EN 50102 |
Indgangstype | Contacts customer voluntary order to transfer to source R |
IP kapslingsklasse | Side: IP30 conforming to EN 60529 Front: 22-26 conforming to EN 60529 Connectors: IP20 conforming to EN 60529 |
Lokal indikering | Fault trip OFF On |
Produkttype | Interface and control unit |
Range of product | Compact NS100...630 Compact NS630b...1600 Masterpact NT Masterpact NW NSX100...250 NSX400...630 |
Selection modes | Circuit breaker on N Circuit breaker on R |
Standarder | IEC 947-5-1 |
Testfunktion | By opening the P25M circuit breaker supplying the controller |
Tillægsfunktioner | Voluntary transfer to replacement source (e.g. energy management commands) Additional contact: transfer to replacement source only if contact is closed |
Udgangstype | Contacts customer: indication of operation in automatic or stop mode |
Yderliger oplysninger:
Se venligst SE katalog©Schneider Electric A/S 2025