Navigér
Sœg

Acti9 iC60LMA 2 poler 40 A Mono terminal MA-karakteristik 15 kA 230/400 V B:36 mm


Varenr:A9F90240
El nr:3322064378
EAN13 nr:3606480085901
Pakning:1stk

[Ics] rated service breaking capacity5 kA 50 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 50 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 50 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 5 kA 50 % x Icu conforming to EN 60947-2 - 440 V AC 50
[In] rated current40 A
[Ue] rated operational voltage440 V AC 50/60 Hz 380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2 500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2 6 kV conforming to EN 60947-2
9 mm pitches4
Ambient air temperature for operation-35...70 °C
Ambient air temperature for storage-40...85 °C
Circuit breaker applicationMotor protection
ColourWhite
Comb busbar distribution block compatibilityYES top or bottom
Connections - terminalsSingle terminal, top or bottom flexible wire(s) 1...25 mm˛ max Single terminal, top or bottom rigid wire(s) 1...35 mm˛ max
Contact position indicatorYes
Breaking capacity30 kA Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 30 kA Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 15 kA Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 10 kA Icu
Control typeToggle
Curve codeMA
Depth78.5 mm
Device short nameIC60L
Earth-leakage protectionSeparate block
Electrical durability10000 cycles
Height85 mm
IP degree of protectionIP20 conforming to EN 60529 IP20 conforming to IEC 60529
Limitation class3 conforming to IEC 60898-1 3 conforming to EN 60898-1
Local signallingTrip indicator
Magnetic tripping limit12 x In +/- 20 %
Mechanical durability20000 cycles
Mounting modeFixed
Mounting supportDIN rail
Network frequency50/60 Hz
Network typeAC
Number of protected poles2
Operating altitude0...2000 m
Overvoltage categoryIV
Period18 months
Poles description2P
Pollution degree3 conforming to IEC 60947-2 3 conforming to EN 60947-2
Product or component typeCircuit breaker
Product weight0.25 kg
Relative humidity95 % ( 55 °C )
RoHS EUR conformity date(YYWW)1001
RoHS EUR statusCompliant
StandardsEN 60947-2 IEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2 Yes conforming to EN 60947-2
Tightening torque3.5 N.m top or bottom
Trip unit technologyMagnetic
Tropicalisation2 conforming to IEC 60068-1
Utilisation categoryCategory A conforming to IEC 60947-2 Category A conforming to EN 60947-2
Width36 mm
Wire stripping length14 mm top or bottom

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info