Navigér
Sœg

Acti9 iC60L 1 pol 20 A Mono terminal Z-karakteristik 25 kA 230 V B:18 mm


Varenr:A9F92120
El nr:3322064679
EAN13 nr:3606480085628
Pakning:1stk

[Ics] rated service breaking capacity12.5 kA 50 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 12.5 kA 50 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % x Icu conforming to IEC 60947-2 - 12...72 V DC 15 kA 100 % x Icu conforming to EN 60947-2 - 12...72 V
[In] rated current20 A
[Ue] rated operational voltage220...240 V AC 50/60 Hz 12...72 V DC 12...60 V AC 50/60 Hz 100...130 V AC 50/60 Hz
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2 500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2 6 kV conforming to EN 60947-2
9 mm pitches2
Ambient air temperature for operation-35...70 °C
Ambient air temperature for storage-40...85 °C
Breaking capacity20 kA Icu conforming to IEC 60947-2 - 12...72 V DC 20 kA Icu conforming to EN 60947-2 - 12...72 V DC 70 kA Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz 70 kA Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz 50 kA Icu conforming to IEC 60947-2
Circuit breaker applicationDistribution
ColourWhite
Comb busbar distribution block compatibilityYES top or bottom
Connections - terminalsSingle terminal, top or bottom flexible wire(s) 1...16 mm˛ max Single terminal, top or bottom rigid wire(s) 1...25 mm˛ max
Contact position indicatorYes
Control typeToggle
Curve codeZ
Depth78.5 mm
Device short nameIC60L
Earth-leakage protectionSeparate block
Electrical durability10000 cycles
Height85 mm
IP degree of protectionIP20 conforming to EN 60529 IP20 conforming to IEC 60529
Limitation class3 conforming to IEC 60898-1 3 conforming to EN 60898-1
Local signallingTrip indicator
Magnetic tripping limit3 x In +/- 20 %
Mechanical durability20000 cycles
Mounting modeFixed
Mounting supportDIN rail
Network frequency50/60 Hz
Network typeAC DC
Number of protected poles1
Operating altitude0...2000 m
Overvoltage categoryIV
Period18 months
Poles description1P
Pollution degree3 conforming to IEC 60947-2 3 conforming to EN 60947-2
Product or component typeCircuit breaker
Product weight0.215 kg
Relative humidity95 % ( 55 °C )
RoHS EUR conformity date(YYWW)1001
RoHS EUR statusCompliant
StandardsEN 60947-2 IEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2 Yes conforming to EN 60947-2
Tightening torque2 N.m top or bottom
Trip unit technologyThermal-magnetic
Tropicalisation2 conforming to IEC 60068-1
Utilisation categoryCategory A conforming to IEC 60947-2 Category A conforming to EN 60947-2
Width18 mm
Wire stripping length14 mm top or bottom

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info