[In] rated current | 40 A |
[Ue] rated operational voltage | 220...240 V AC 50/60 Hz 12...72 V DC 12...60 V AC 50/60 Hz 100...130 V AC 50/60 Hz |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 500 V AC 50/60 Hz conforming to EN 60947-2 |
[Ics] rated service breaking capacity | 10 kA 50 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 35 kA 50 % x Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz 18 kA 50 % x Icu conforming to IEC 60947-2 - 100...130 V AC 50/60 Hz 10 kA 50 % x Icu conforming to EN 60947-2 - 220... |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 6 kV conforming to EN 60947-2 |
9 mm pitches | 2 |
Ambient air temperature for operation | -35...70 °C |
Ambient air temperature for storage | -40...85 °C |
Breaking capacity | 20 kA Icu conforming to IEC 60947-2 - 12...72 V DC 20 kA Icu conforming to EN 60947-2 - 12...72 V DC 70 kA Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz 70 kA Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz 36 kA Icu conforming to IEC 60947-2 |
Circuit breaker application | Distribution |
Colour | White |
Comb busbar distribution block compatibility | YES top or bottom |
Connections - terminals | Single terminal, top or bottom flexible wire(s) 1...25 mm˛ max Single terminal, top or bottom rigid wire(s) 1...35 mm˛ max |
Contact position indicator | Yes |
Control type | Toggle |
Curve code | Z |
Depth | 78.5 mm |
Device short name | IC60L |
Earth-leakage protection | Separate block |
Electrical durability | 10000 cycles |
Height | 85 mm |
IP degree of protection | IP20 conforming to EN 60529 IP20 conforming to IEC 60529 |
Limitation class | 3 conforming to IEC 60898-1 3 conforming to EN 60898-1 |
Local signalling | Trip indicator |
Magnetic tripping limit | 3 x In +/- 20 % |
Mechanical durability | 20000 cycles |
Mounting mode | Fixed |
Mounting support | DIN rail |
Network frequency | 50/60 Hz |
Network type | AC DC |
Number of protected poles | 1 |
Operating altitude | 0...2000 m |
Overvoltage category | IV |
Period | 18 months |
Poles description | 1P |
Pollution degree | 3 conforming to IEC 60947-2 3 conforming to EN 60947-2 |
Product or component type | Circuit breaker |
Product weight | 0.215 kg |
Relative humidity | 95 % ( 55 °C ) |
RoHS EUR conformity date(YYWW) | 1001 |
RoHS EUR status | Compliant |
Standards | EN 60947-2 IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 Yes conforming to EN 60947-2 |
Tightening torque | 3.5 N.m top or bottom |
Trip unit technology | Thermal-magnetic |
Tropicalisation | 2 conforming to IEC 60068-1 |
Utilisation category | Category A conforming to IEC 60947-2 Category A conforming to EN 60947-2 |
Width | 18 mm |
Wire stripping length | 14 mm top or bottom |