Automatsikring C120N 4 poler 100 A Mono terminal D-karakteristik 10kA 230/400 V B:108 mm


Varenr:A9N18392
El nr:3322067414
EAN13 nr:3606480379635
Pakning:1stk

[In] rated current100 A at 30 °C
[Ue] rated operational voltage415 V AC 50/60 Hz
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity15 kA 75 % x Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % x Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % x Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
9 mm pitches12
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...85 °C
Breaking capacity10 kA Icu conforming to EN/IEC 60947-2 - <= 500 V DC 20 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 10 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 6 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Circuit breaker applicationDistribution
ColourWhite
Comb busbar distribution block compatibilityNO
Connections - terminalsTunnel type terminals flexible wire(s) 1.5...35 mm˛ max Tunnel type terminals rigid wire(s) 1...50 mm˛ max
Contact position indicatorYes
Control typeToggle
Curve codeD
Depth73 mm
Device short nameC120N
Earth-leakage protectionSeparate block
Electrical durability5000 cycles conforming to IEC 60947-2
Electrical shock protection classClass III
Height81 mm
IP degree of protectionIP20 conforming to IEC 60529
Limitation class3 conforming to EN/IEC 60947-2
Local signallingON/OFF indication
Magnetic tripping limit10...14 x In
Mechanical durability20000 cycles
Mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
Network frequency50/60 Hz
Network typeAC
Number of protected poles4
Operating altitude2000 m
Period18 months
Poles description4P
Pollution degree3 conforming to IEC 60947-2
Product certificationsGOST
Product or component typeCircuit breaker
Product weight0.82 kg
Quality labelsNF
Range of productC120
Relative humidity95 % 55 °C
StandardsEN/IEC 60947-2 IEC 60898-1
Suitability for isolationYes conforming to IEC 60947-2
Tightening torque3.5 N.m
Trip unit technologyThermal-magnetic
Tropicalisation2 conforming to IEC 60068-1
Width108 mm
Wire stripping length15 mm