Navigér
Sœg

Vigi iC60 fejlstrĝmsmodul 2 poler 25 A 30 mA klasse A B:27 mm


Varenr:A9W21225
El nr:3322069331
EAN13 nr:3606480443404
Pakning:1stk

[In] rated current25 A
[Ue] rated operational voltage230/415 V AC 50/60 Hz conforming to IEC 61009-1 230/400 V AC 50/60 Hz conforming to EN 61009-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
9 mm pitches3
Ambient air temperature for operation-25...60 °C
Ambient air temperature for storage-40...85 °C
ColourWhite
Connections - terminalsTunnel type terminals downside 1...16 mm² flexible Tunnel type terminals downside 1...25 mm² rigid
Depth74 mm
Device location in systemOutgoer
Device short nameVigi iC60
Earth-leakage protection classClass A
Earth-leakage protection time delayInstantaneous
Earth-leakage sensitivity30 mA
Electrical connection to mcbBy screws
Electromagnetic compatibility8/20 µs impulse withstand 250 A conforming to IEC 61009-1
Height91 mm
IP degree of protectionIP20 conforming to IEC 60529
Local signallingTrip indicator
Mounting modeClip-on
Mounting supportDIN rail
Network frequency50/60 Hz
Network typeAC
Overvoltage protectionWithout
Period18 months
Poles description2P
Pollution degree3 conforming to IEC 60947-2
Product compatibilityDouble terminal
Product or component typeEarth leakage add-on block
Product weight0.165 kg
Residual current tripping technologyVoltage independent
StandardsEN 61009-1 IEC 61009-1
Tightening torque2 N.m
Width63 mm
Wire stripping length14 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info