Vigi iC60 fejlstrĝmsmodul 2 poler 25 A 100 mA klasse A B:27 mm

Varenr: | A9W22225 |
El nr: | 3322069399 |
EAN13 nr: | 3606480443619 |
Pakning: | 1stk |
 |
[In] rated current | 25 A |
[Ue] rated operational voltage | 230/415 V AC 50/60 Hz conforming to IEC 61009-1 230/400 V AC 50/60 Hz conforming to EN 61009-1 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
9 mm pitches | 3 |
Ambient air temperature for operation | -25...60 °C |
Ambient air temperature for storage | -40...85 °C |
Colour | White |
Connections - terminals | Tunnel type terminals downside 1...16 mm² flexible Tunnel type terminals downside 1...25 mm² rigid |
Depth | 74 mm |
Device location in system | Outgoer |
Device short name | Vigi iC60 |
Earth-leakage protection class | Class A |
Earth-leakage protection time delay | Instantaneous |
Earth-leakage sensitivity | 100 mA |
Electrical connection to mcb | By screws |
Electromagnetic compatibility | 8/20 µs impulse withstand 250 A conforming to IEC 61009-1 |
Height | 91 mm |
IP degree of protection | IP20 conforming to IEC 60529 |
Local signalling | Trip indicator |
Mounting mode | Clip-on |
Mounting support | DIN rail |
Network frequency | 50/60 Hz |
Network type | AC |
Overvoltage protection | Without |
Period | 18 months |
Poles description | 2P |
Pollution degree | 3 conforming to IEC 60947-2 |
Product compatibility | Double terminal |
Product or component type | Earth leakage add-on block |
Product weight | 0.165 kg |
Residual current tripping technology | Voltage independent |
Standards | EN 61009-1 IEC 61009-1 |
Tightening torque | 2 N.m |
Width | 63 mm |
Wire stripping length | 14 mm |
Yderliger oplysninger:
Se venligst SE katalog©Schneider Electric A/S 2025