[Us] rated supply voltage | 24 V DC +/- 20 % |
Absolute accuracy error | +/- 1 % of full scale for analog input 12 bits |
Ambient air temperature for operation | -25...60 °C |
Ambient air temperature for storage | -40...85 °C |
Application specific I/O | Pulse totalising counter Pulse converter |
Colour | White (RAL 9003) |
Clamping connection capacity | 2 x 0.2...2 x 1.5 mm˛, rigid without cable end for supply circuit 2 x 0.2...2 x 1.5 mm˛, rigid with cable end for supply circuit 2 x 0.2...2 x 1.5 mm˛, flexible without cable end for supply circuit 2 x 0.2...2 x 1.5 mm˛, flexible with cable end for supply |
Commercial Status | Commercialised |
Communication network type | Ethernet, Modbus TCP/IP, server with connector RJ45 at 10, 100 Mbit/s RS485, Modbus RTU, master with connector SUB-D 9 at 9.6...19.2 kbauds |
Connections - terminals | RJ45 connector qty: 1 for ETHERNET, ordered separately Plug-in connector qty: 1 for analog input Spring-loaded terminal Ti24 qty: 7 for digital input/output, ordered separately Plug-in connector qty: 1 for communication bus Plug-in connector qty: 1 for su |
Depth | 40 mm |
Device short name | Acti 9 Smartlink |
Electromagnetic compatibility | Conducted emission, class A at 0.15...30 MHz conforming to IEC 61131-2 Radiated emission, class A at 30...1000 MHz conforming to IEC 61131-3 Ed.3 Immunity to magnetic fields at network frequency at 30 A/m conforming to IEC 61000-4-8 Conducted EMC at 10 V |
Electronic filtering time | For analog input For digital input |
Group of channels | 1 group of 7 digital channels 1 group of 1 analog channel |
Height | 23 mm |
Immunity to microbreaks | 10 ms |
Input type | Current sink for digital input, 24 V DC +/- 20 % at 2.5 mA Voltage for analog input, 0...10 V DC Current for analog input, 4...20 mA |
Input/output type | 2 inputs + 1 output per digital channel 2 inputs per analog channel |
Inrush current | 0.5 A for digital output |
Inrush current | 3 A |
Leakage current | 0.1 mA for digital output |
Local signalling | 1 LED green, orange and red color for status 1 LED green and yellow color for communication (LK/ACT 10/100) 1 LED green, orange and red color for NS (Network Status) 1 LED yellow color for communication |
Location of connection | Front |
Maximum permanent current | 0.005 A for digital input |
Mounting position | Horizontal Vertical |
Mounting support | DIN rail |
Operating altitude | 2000 m |
Output type | Logic current source at 24 V DC, 100 mA |
Pollution degree | 3 |
Product compatibility | 200 A multiclip 80 A multiclip Reflex iC60 IACT 24 IATL 24 IOF+SD 24 OF+SD 24 RCA |
Protection type | Against reverse polarity for input Against reverse polarity for auxiliary supply Short-circuit protection for digital output Overvoltage at <= 33 V DC for digital output |
Relative humidity | 90 % at 40 °C |
Reset | Factory reset on front face |
Standards | EN/IEC 61131-2 EN/IEC 62053-31 |
Supply current | 1.5 A |
Tropicalisation | 2 |
Voltage drop | < 1 V for digital output |
Web server | Embedded |
Width | 359 mm |
Wire stripping length | 7 mm for analog input 7 mm for supply circuit 7 mm for communication bus 10 mm for control |