[Us] rated supply voltage | 24 V DC +/- 20 % |
Ambient air temperature for operation | -25...60 °C |
Ambient air temperature for storage | -40...80 °C |
Application specific I/O | Pulse totalising counter Pulse converter |
Colour | White (RAL 9003) |
Communication port protocol | Modbus RTU, RS485 slave 9.6...38.4 kbauds |
Connections - terminals | Plug-in connector for communication bus, located on front, 3 twisted shielded cables 0.25 mm˛ rigid without cable end 2 Plug-in connector for communication bus, located on front, 3 twisted shielded cables 0.25 mm˛ rigid with cable end 2 Plug-in connector |
Depth | 40 mm |
Device short name | Acti 9 Smartlink |
Electromagnetic compatibility | Immunity to magnetic fields at network frequency 30 A/m conforming to IEC 61000-4-8 Conducted EMC 10 V, 0.15...80 MHz conforming to IEC 61000-4-6 Resistance to fast transient 1 kV for I/O and Modbus/2 kV for 24 V DC power supply 5...100 kHz conforming to |
Electronic filtering time | 1 ms for input |
Group of channels | 1 group of 11 channels |
Height | 23 mm |
Immunity to microbreaks | 10 ms |
Input type | Current sink at 24 V DC (+/- 20 %)0.0025 A |
Input/output type | 2 inputs + 1 output per channel |
Inrush current | 0.5 A for output |
Inrush current | 3 A |
IP degree of protection | IP20 |
Leakage current | 0.1 mA for output |
Local signalling | Status, color: red Status, color: orange Status, color: green COM, color: orange |
Maximum permanent current | 0.005 A for input |
Mounting mode | Horizontal |
Mounting support | 35 mm symmetrical DIN rail |
Operating altitude | 2000 m |
Output type | Logic current source at 24 V DC 100 mA |
Overvoltage protection | With, 33 V DC max for output |
Period | 18 months |
Pollution degree | 3 |
Product compatibility | 200 A multiclip 80 A multiclip |
Product or component type | Modbus RS485 smart communication I/O module |
Protection type | Against reverse polarity for input Against reverse polarity for auxiliary supply |
Range of product | IC60 ICT IDPN IID ITL Reflex iC60 ISW-NA IC120 Acti 9 Smartlink |
Relative humidity | 90 % (40 °C) |
Reset | Factory reset on front face |
RoHS EUR conformity date(YYWW) | 1201 |
RoHS EUR status | Compliant |
Short-circuit protection | With output |
Standards | EN/IEC 61131-2 EN/IEC 62053-31 |
Supply current | 1.5 A |
Tropicalisation | 2 |
Type of setting | Reset plug in, plug out the auxiliary supply Reset address encoders Modbus address 01...99 address encoders |
Voltage drop | < 1 V for output |
Width | 359 mm |
Wire stripping length | 7 mm for auxiliary supply 7 mm for communication bus 10 mm for control |