Frekvensomformer 160 kW 3x400 V IP21


Varenr:ATV630C16N4
El nr:7565721241
EAN13 nr:null
Pakning:0stk

[Us] rated supply voltage380...480 V (- 15...10 %)
Acceleration and deceleration rampsLinear adjustable separately from 0.01 to 9000 s S, U or customized
AccuracyAnalog output AO1, AO2 : +/- 1 % for a temperature variation 60 °C Analog input AI1, AI2, AI3 : +/- 0.6 % for a temperature variation 60 °C
Ambient air temperature for operation50...60 °C with derating factor -15...50 °C without derating
Ambient air temperature for storage-40...70 °C
Analogue input number3
Analogue input typeSoftware-configurable current AI1, AI2, AI3 : 0...20 mA impedance 250 Ohm, resolution 12 bits Software-configurable voltage AI1, AI2, AI3 : 0...10 V DC impedance 30 kOhm, resolution 12 bits
Analogue output number2
Analogue output typeSoftware-configurable current AO1, AO2 : 0...20 mA, resolution 10 bits Software-configurable voltage AO1, AO2 : 0...10 V DC impedance 470 Ohm, resolution 10 bits
Apparent power161.396 kVA at 480 V (heavy duty application) 201.297 kVA at 480 V (normal duty application)
Asynchronous motor control profileConstant torque standard Variable torque standard Optimized torque mode
Braking to standstillBy DC injection
Communication port protocolEthernet Modbus serial Modbus TCP
Continuous output current240 A at 2.5 kHz (heavy duty application) 302 A at 2.5 kHz (normal duty application)
Data format8 bits, configurable odd, even or no parity for Modbus serial
Depth390 mm
Device short nameATV630
Discrete input number8
EMC filterIntegrated conforming to EN/IEC 61800-3 category C3 with 150 m motor cable maxi
Environmental characteristicDust pollution resistance class 3S3 EN/IEC 60721-3-3 Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Discrete input logicSTOA, STOB, positive logic (source) : , < 5 V (state 0), > 11 V (state 1) DI5, DI6, positive logic (source) : , < 0.6 V (state 0), > 2.5 V (state 1) DI1...DI6, negative logic (sink) : , > 16 V (state 0), < 10 V (state 1) DI1...DI6, positive logic (source)
Discrete input typeSafe torque off STOA, STOB : 24 V DC <= 30 V impedance > 2.2 kOhm Programmable as pulse input DI5, DI6 0...30 kHz : 24 V DC <= 30 V Programmable DI1...DI6 : 24 V DC <= 30 V impedance 3.5 kOhm
Electrical connectionMotor : screw terminal 2 x 95...3 x 120 mm² (AWG 3/0...300 kcmil) Line side : screw terminal 2 x 95...3 x 120 mm² (AWG 3/0...300 kcmil) Control : removable screw terminals 0.5...1.5 mm² (AWG 20...AWG 16)
Electromagnetic compatibilityConducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3 1.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4 Radiated radio-freque
Exchange modeHalf duplex, full duplex, autonegotiation for Ethernet/Modbus TCP
Frequency resolutionAnalog input : 0.012/50 Hz Display unit : 0.1 Hz
Height853 mm
Input compatibilityDiscrete input STOA, STOB : level 1 PLC conforming to EN/IEC 61131-2 Discrete input DI5, DI6 : level 1 PLC conforming to IEC 65A-68 Discrete input DI1...DI6 : level 1 PLC conforming to EN/IEC 61131-2
Insulation resistance> 1 mOhm at 500 V DC for 1 minute to earth
IP degree of protectionIP00 conforming to IEC 60529 IP00 conforming to IEC 61800-5-1
IsolationBetween power and control terminals
Line current213 A at 480 V (heavy duty application) 237 A at 380 V (heavy duty application) 262 A at 480 V (normal duty application) 284 A at 380 V (normal duty application)
Linearity errorAnalog output AO1, AO2 : +/- 0.2 % Analog input AI1, AI2, AI3 : +/- 0.15 % of maximum value
Local signalling1 LED red for presence of voltage 4 LEDs dual colour for communication module status 3 LEDs dual colour for embedded communication status 3 LEDs for local diagnostic
MarkingCE
Maximum switching currentRelay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at 30 V DC Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at 250 V AC Relay output R1, R2, R3 on resistive load (cos phi = 1) : 3 A at 30 V DC R
Maximum transient current360 A during 60 s (heavy duty application) 332.2 A during 60 s (normal duty application)
Method of accessSlave for Modbus TCP
Minimum switching currentRelay output R1, R2, R3 : 5 mA at 24 V DC
Motor power hp200 hp (heavy duty application) 250 hp (normal duty application)
Motor power kW132 kW (heavy duty application) 160 kW (normal duty application)
Motor slip compensationAdjustable Automatic whatever the load Can be suppressed Not available in permanent magnet motor law
Mounting modeCabinet mount
Network number of phases3 phases
Noise level76 dB conforming to 86/188/EEC
Nominal switching frequency2.5 kHz
Number of addresses1...247 for Modbus serial
Number of preset speeds16 preset speeds
Operating altitude1000...4800 m with current derating 1 % per 100 m <= 1000 m without derating
Operating positionVertical +/- 10 degree
Output voltage<= power supply voltage
Physical interface2-wire RS 485 for Modbus serial
Option cardSlot A/slot B : relay output card Slot A/slot B : digital or analog I/O extension card Slot A : communication card for CANopen screw terminals Slot A : communication card for CANopen SUB-D 9 Slot A : communication card for CANopen daisy chain RJ45 Slot A
Pollution degree2 conforming to EN/IEC 61800-5-1
Power dissipation in W3270 W (forced convection) at 380 V switching frequency 2.5 kHz
Product certificationsCSA TÜV UL REACH
Product destinationAsynchronous motors Synchronous motors
Product or component typeVariable speed drive
Product specific applicationProcess and utilities
Product weight82 kg
Prospective line Isc50 kA
Protection typeDrive : break on the control circuit Drive : overspeed Drive : line supply phase loss Drive : line supply undervoltage Drive : line supply overvoltage Drive : overvoltages on the DC bus Drive : motor phase break Drive : short-circuit protection Drive : ov
Range of productAltivar Process
Refresh timeRelay output R1, R2, R3 : 5 ms (+/- 0.5 ms)
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Relay output number3
Relay output typeConfigurable relay logic R3 : sequence relay NO electrical durability 100000 cycles Configurable relay logic R2 : sequence relay NO electrical durability 100000 cycles Configurable relay logic R1 : fault relay NO/NC electrical durability 100000 cycles
Safety functionSTO (safe torque off) SIL 3
Sampling durationAnalog output AO1 : 10 ms (+/- 1 ms) Analog input AI1, AI2, AI3 : 5 ms (+/- 0.1 ms) Discrete input DI5, DI6 : 5 ms (+/- 1 ms) Discrete input DI1...DI4 : 2 ms (+/- 0.5 ms)
Shock resistance15 gn during 11 ms conforming to IEC 60068-2-27
Speed drive output frequency0.1...500 Hz
StandardsIEC 13849-1 IEC 61508 IEC 60721-3 IEC 61000-3-12 EN/IEC 61800-5-1 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 UL 508C
SupplyInternal supply for digital inputs and STO : 24 V DC (21...27 V) current <= 200 mA (overload and short-circuit protection) Internal supply for reference potentiometer (1 to 10 kOhm) : 10.5 V DC +/- 5 % current <= 10 mA (overload and short-circuit protecti
Supply frequency50...60 Hz (+/-5 %)
Switching frequency2...8 kHz adjustable 2.5...8 kHz with derating factor
Synchronous motor control profilePermanent magnet motor
THDI<= 48 % full load conforming to IEC 61000-3-12
Transmission frameRTU for Modbus serial
Transmission rate4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial 10/100 Mbit/s for Ethernet IP/Modbus TCP
Type of connectorRJ45 (on the remote graphic terminal) for Modbus serial RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
Type of coolingForced convection
Type of polarizationNo impedance for Modbus serial
VariantStandard version
Vibration resistance1 gn (f = 13...200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f = 2...13 Hz) conforming to IEC 60068-2-6
Volume of cooling air600 m3/h
Width320 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog