[Us] rated supply voltage | 500...690 V (- 15...10 %) |
Accellerations- og nedreguleringsrampe | Automatic adaptation of ramp if braking capacity exceeded, by using resistor Linear adjustable separately from 0.01 to 9000 s S, U or customized |
Accuracy | +/- 1 % (AO1) for a temperature variation 60 °C +/- 0.6 % (AI2) for a temperature variation 60 °C +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C |
Adskillelse | Electrical between power and control |
Afkølingsmåde | Water cooled |
Ambient air temperature for operation | -10...50 °C without derating |
Ambient air temperature for storage | -25...70 °C |
Analog indgangstype | Software-configurable voltage: (AI2) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 11 bits Software-configurable current: (AI2) 0...20 mA - 242 Ohm - resolution: 11 bits Bipolar differential voltage: (AI1-/Al1+) +/- 10 V DC - 24 V max - resolution: 11 |
Analog udgangstype | Software-configurable logic output: (AO1) 10 V - <= 20 mA Software-configurable current: (AO1) 0...20 mA - 500 Ohm - resolution: 10 bits Software-configurable voltage: (AO1) 0...10 V DC - 470 Ohm - resolution: 10 bits |
Analoge Indgange | 2 |
Analoge udgange | 1 |
Antal adresser | 1...127 addresses for CANopen 1...247 addresses for Modbus |
Antal digitale udgange | 2 |
Anvendes til | Asynchronous motors Synchronous motors |
Bredde | 330 mm |
Bremsemoment | < 150 % with braking or hoist resistor 30 % without braking resistor |
Bremsning ved stilstand | Med DC indsprøjtning |
Cooling fluid type | Water-glycol mixture Clean water Industrial water |
Dataformat | 8 bits, odd even or no configurable parity for Modbus på terminal 8 bits, 1 stop, even parity for Modbus on front face |
Dielektrisk gennemslagsholdbarhed | 5345 V DC between control and power terminals 3110 V DC between earth and power terminals |
Asynkron motorkontrol | Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor, ENA (energy Adaptation) system Flux vector control |
Beskyttelsestype | Power removal for Motor Motor fase brud for Motor Thermal protection for Motor Imod løs fase for køre Line supply overvoltage for køre Line supply undervoltage for køre Imod overskridende maks. Hastighed for køre Break on the control circuit for køre Over |
Digital indgangslogik | Positive logic (source) (PWR) , < 2 V (state 0), > 17 V (state 1) Negative logic (sink) (LI6) if configured as logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source) (LI6) if configured as logic input, < 5 V (state 0), > 11 V (state 1) Ne |
Digital indgangsnummer | 7 |
Digital indgangstype | Safety input (PWR) 24 V DC - 1500 Ohm conforming to ISO 13849-1 level d Switch-configurable PTC probe (LI6) - 0...6 probes - 1500 Ohm Kontakt-konfiguration (LI6) 24 V DC, with level 1 PLC - 3500 Ohm Programmering (LI1...LI5) 24 V DC, with level 1 PLC - 35 |
Digital udgangstype | Configurable relay logic: (R2A, R2B) No - 100000 cycles Configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles |
Driftshøjde | 1000...2260 m with current derating 1 % per 100 m <= 1000 m without derating |
Driftsstilling | Vertical +/- 10 degree |
Dybde | 377 mm |
Electromagnetisk kompatibilitet | Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Conducted radio-frequency immunity test Level 3 conforming to IEC 61000-4-6 1.2/50 µs - 8/20 µs surge immunity test Level 3 conforming to IEC 61000-4-5 Electrical fast transient/bur |
Elektrisk tilslutning | Terminal 120 mm² (PA, PB) Terminal 2 x 120 mm² (PC/-, PO, PA/+) Terminal 2 x 120 mm² (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3) Terminal 2.5 mm2 / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) |
EMC filter | Integrated |
Enhedens korte navn | ATV71Q |
Faseantal | 3 faser |
Flow velocity | 8 l/min |
Forsyning | Internal supply: 24 V DC (21...27 V) - <= 200 mA with overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 % - <= 10 mA with overload and short-circuit protection |
Forsyningsspændingsgrænser | 425...759 V |
Forureningsgrad | 3 conforming to UL 840 2 conforming to EN/IEC 61800-5-1 |
Frekens | 2.5...4.9 kHz with derating factor 2...4.9 kHz Justerbar |
Fysisk interface | 2-wire RS 485 for Modbus |
Hastighedsområde | 1...1000 asynchronous motor in closed-loop mode with encoder feedback 1...50 synchronous motor in open-loop mode, without speed feedback 1...100 asynchronous motor in open-loop mode, without speed feedback |
Hyppig beslutning | 0.024/50 Hz for analog indgang 0.1 Hz for display enhed |
Højde | 950 mm |
IP kapslingsklasse | IP54 on lower part conforming to EN/IEC 60529 IP54 on lower part conforming to EN/IEC 61800-5-1 IP30 on side parts conforming to EN/IEC 60529 IP30 on side parts conforming to EN/IEC 61800-5-1 IP30 on the front panel conforming to EN/IEC 60529 IP30 on the |
Isolationsmodstand | > 1 mOhm at 500 V DC for 1 minute to earth |
Klemmetype | 1 RJ45 for CANopen 1 RJ45 for Modbus på terminal 1 RJ45 for Modbus on front face |
Linearitetsfejl | +/- 0.2 % (AO1) +/- 0.15 % of maximum value (AI1-/Al1+, AI2) |
Lokal indikering | 1 LED - rød - drive voltage |
Maximum transient current | 330 A for 2 s - 3 faser 300 A for 60 s - 3 faser |
Ledningstype | UL 508 cable with a NEMA Type1 kit: 3 wire(s) - 40 °C, copper 75 °C / PVC IEC cable with an IP21 or an IP31 kit: 3 wire(s) - 40 °C, copper 70 °C / PVC IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 70 °C / PVC IEC cable without mounting kit: 1 |
Maximum sluttestrøm | 2 A at 30 V DC on inductiv load - cos phi = 0.4 - L/R = 7 ms (R1, R2) 2 A at 250 V AC on inductiv load - cos phi = 0.4 - L/R = 7 ms (R1, R2) 5 A at 30 V DC on modstandsdygtig load - cos phi = 1 - L/R = 0 ms (R1, R2) 5 A at 250 V AC on modstandsdygtig load |
Minimum sluttestrøm | 3 mA at 24 V DC (configurable relay logic) |
Motor cable length | <= 400 m unshielded cable with motor choke <= 250 m skærm kabel with motor choke <= 30 m unshielded cable without motor choke <= 15 m skærm kabel without motor choke |
Motor slip compensation | Justerbar Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) Suppressable |
Motoreffekt i kW | 160 KW 3 faser for 690 V 132 KW 3 faser for 500 V |
Mærkning | CE |
Netfrekvensgrænse | 47.5...63 Hz |
Nominal switching frequency | 2.5 kHz |
Option card | Overhead crane card Controller inside programmable card I/O extension card Interface card for encoder Kommunikation kort for CC-Link Kommunikation kort for Interbus-S Kommunikation kort for Profibus DP V1 Kommunikation kort for Profibus DP Kommunikation k |
Polaritetstype | No impedance for Modbus |
Pressure drop | <= 1.5 bar |
Product specific application | Complex, high-power machines |
Productcertificeringer | CSA C-Tick GOST NOM 117 UL |
Produkttype | Frekvensomformer |
Prospektiv kortslutningsstrøm Isc | <= 35 kA for 3 faser |
Protokol for kommunikationsport | CANopen Modbus |
Prøvevarighed | 2 ms +/- 0.5 ms (Al2) for analog udgang 2 ms +/- 0.5 ms (AI1-/Al1+) for analog udgang 2 ms +/- 0.5 ms (LI6) if configured as logic input for separat indgang 2 ms +/- 0.5 ms (LI1...LI5) for separat indgang |
Range of product | Altivar 71Q |
Reaktionstid | <= 100 ms in STO (Safe Torque Off) 2 ms +/- 0.5 ms (AO1) 7 ms +/- 0.5 ms (R2A, R2B) 7 ms +/- 0.5 ms (R1A, R1B, R1C) |
Regulation loop | Adjustable PI regulator |
Relativ fugtighed | 5...95 % without dripping water conforming to IEC 60068-2-3 5...95 % without condensation conforming to IEC 60068-2-3 |
Sammenbygningens type | With heat sink |
Shockmodstand | 7 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Speed accuracy | +/- 10 % of nominal slip for 0.2 Tn to Tn torque variation, without speed feedback +/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation, in closed-loop mode with encoder feedback |
Speed drive output frequency | 0.1...500 Hz |
Standarder | EN 55011 class A group 2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3-3 klasse 3C2 ISO 13849-1 level d UL Type 1 IEC 61508 SIL2 |
Støjgrænse | 77 dB conforming to 86/188/EEC |
Synkronmotorkontrol | Vector control without sensor, standard Vector control with sensor, standard |
Termisk tab | 480 W 100 % of line current for area of air cooling (control part) 2600 W 100 % of line current for area of liquid cooling (power part) |
Tilgangs metode | Slave for CANopen |
Tilgangsstrøm | 163 A for 690 V 3 faser / 160 KW 182 A for 500 V 3 faser / 132 KW |
Tilslutningsfrekvens | 50...60 Hz (- 5...5 %) |
Torque accuracy | +/- 15 % in open-loop mode, without speed feedback +/- 5 % in closed-loop mode with encoder feedback |
Tilspændingsmoment | 24 N.m, 212 lb.in (PA, PB) 24 N.m, 212 lb.in (PC/-, PO, PA/+) 24 N.m, 212 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3) 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) |
Transient overmoment | 220 % of nominal motor torque, +/- 10 % for 2 s 170 % of nominal motor torque, +/- 10 % for 60 s |
Transmissionsstel | RTU for Modbus |
Transmissionsstørrelse | 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus på terminal 9600 bps, 19200 bps for Modbus on front face |
Udgangsspænding | <= power supply voltage |
Variant | Reinforced version |
Vedvarende udgangsstrøm | 180 A at 2.5 kHz, 690 V - 3 faser 200 A at 2.5 kHz, 500 V - 3 faser |
Vibrationsmodstand | 0.6 gn (f = 10...200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm peak to peak (f = 3...10 Hz) conforming to EN/IEC 60068-2-6 |
Volume of fluid | 0.2 l |
Vægt | 80 kg |
Væsketemperatur | 5...55 °C |