[Ith] conventional free air thermal current | 10 A at <= 50 °C |
[Ue] rated operational voltage | <= 690 V <= 400 Hz |
[Ui] rated insulation voltage | 600 V conforming to CSA C22.2 No 14 690 V conforming to BS 5424 750 V conforming to VDE 0110 group C 690 V conforming to IEC 60947 |
Ambient air temperature for operation | -25...50 °C |
Ambient air temperature for storage | -50...80 °C |
Associated fuse rating | 10 A gG conforming to VDE 0660 10 A gG conforming to IEC 60947 |
Connections - terminals | Spring terminals 1 cable(s) 0.75...1.5 mm² - cable stiffness: flexible - without cable end Spring terminals 1 cable(s) 0.75...1.5 mm² - cable stiffness: solid |
Contactor application | Control circuit |
Control circuit type | AC 50/60 Hz |
Control circuit voltage | 230 V AC 50/60 Hz |
Control circuit voltage limits | 0.8...1.15 Uc at 50 °C operational 0.2...0.75 Uc at 50 °C drop-out |
Depth | 57 mm |
Device short name | CA2K |
Flame retardance | Requirement 2 conforming to NF F 16-102 Requirement 2 conforming to NF F 16-101 V1 conforming to UL 94 |
Heat dissipation | 1.3 W |
Height | 58 mm |
Hold-in power consumption in VA | 4.5 VA at 20 °C |
Immunity to microbreaks | 2 ms |
Inrush power in VA | 30 VA at 20 °C |
Insulation resistance | > 10 MOhm |
Irms rated making capacity | 110 A conforming to IEC 60947 |
Mechanical durability | 10 Mcycles |
Mechanical robustness | Shocks contactor closed 15 Gn for 11 ms IEC 60068-2-27 Shocks contactor open 10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor open 2 Gn, 5...300 Hz IEC 60068-2-6 |
Minimum switching current | 5 mA |
Minimum switching voltage | 17 V |
Mounting support | Plate Rail |
Non overlap distance | 0.5 mm |
Operating altitude | 2000 m without derating in temperature |
Operating rate | 10000 cyc/h |
Operating time | 10...20 ms coil energisation and NO closing 10...20 ms coil de-energisation and NO opening |
Pole contact composition | 4 NO |
Product certifications | CSA UL |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product name | TeSys CAK |
Product or component type | Control relay |
Product weight | 0.18 kg |
Protective treatment | TC conforming to IEC 60068 |
Range | TeSys |
REACh | Reference not containing SVHC above the threshold |
RoHS | Compliant - since 0644 - Schneider Electric declaration of conformity |
Standards | BS 5424 IEC 60947 NF C 63-140 VDE 0660 |
Sustainable offer status | Green Premium product |
Utilisation category | AC-15 DC-13 |
Width | 45 mm |