Navigér
Sœg

TeSys K hjælperelæ - 2 NO + 2 NC - <= 690 V - 220 V DC


Varenr:CA3KN22MD
El nr:7522026934
EAN13 nr:3389110483932
Pakning:1stk

[Ith] conventional free air thermal current10 A at <= 50 °C
[Ue] rated operational voltage<= 690 V <= 400 Hz
[Ui] rated insulation voltage600 V conforming to CSA C22.2 No 14 690 V conforming to BS 5424 750 V conforming to VDE 0110 group C 690 V conforming to IEC 60947
Ambient air temperature for operation-25...50 °C
Ambient air temperature for storage-50...80 °C
Associated fuse rating10 A gG conforming to VDE 0660 10 A gG conforming to IEC 60947
Connections - terminalsScrew clamp terminals 2 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - without cable end Screw clamp terminals 1 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - with cable end Screw clamp terminals 2 cable(s) 0.75...4 mm² - cable stiffness: f
Contactor applicationControl circuit
Control circuit typeDC standard
Control circuit voltage220 V DC
Control circuit voltage limits0.1...0.75 Uc at 50 °C drop-out 0.8...1.15 Uc at 50 °C operational
Depth57 mm
Device short nameCA3K
Flame retardanceRequirement 2 conforming to NF F 16-102 Requirement 2 conforming to NF F 16-101 V1 conforming to UL 94
Heat dissipation3 W
Height58 mm
Hold-in power consumption in W3 W at 20 °C
Immunity to microbreaks2 ms
Inrush power in W3 W at 20 °C
Insulation resistance> 10 MOhm
IP degree of protectionIP2x
Irms rated making capacity110 A conforming to IEC 60947
Mechanical durability20 Mcycles
Minimum switching current5 mA
Minimum switching voltage17 V
Mounting supportPlate Rail
Non overlap distance0.5 mm
Operating altitude2000 m without derating in temperature
Operating rate10000 cyc/h
Pole contact composition2 NO + 2 NC
Product certificationsCSA UL
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Mechanical robustnessShocks contactor closed 15 Gn for 11 ms IEC 60068-2-27 Shocks contactor open 10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor open 2 Gn, 5...300 Hz IEC 60068-2-6
Operating time25...35 ms coil energisation and NC opening 15 ms coil de-energisation and NC closing 30...40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening
Product nameTeSys CAK
Product or component typeControl relay
Product weight0.225 kg
Protective treatmentTC conforming to IEC 60068
RangeTeSys
REAChReference not containing SVHC above the threshold
RoHSCompliant - since 0640 -  Schneider Electric declaration of conformity
StandardsBS 5424 IEC 60947 NF C 63-140 VDE 0660
Sustainable offer statusGreen Premium product
Tightening torque1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 6 mm 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Utilisation categoryAC-15 DC-13
Width45 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog