[Icw] rated short-time withstand current | 140 A 100 ms 120 A 500 ms 100 A 1 s |
[Ith] conventional free air thermal current | 10 A at <= 60 °C |
[Ue] rated operational voltage | <= 690 V AC 25...400 Hz |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1 600 V certifications CSA 600 V certifications UL |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
Ambient air temperature for operation | -40...70 °C |
Ambient air temperature for storage | -60...80 °C |
Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
Contactor application | Control circuit |
Control circuit type | DC standard |
Control circuit voltage | 24 V DC |
Control circuit voltage limits | 0.1...0.25 Uc drop-out 0.7...1.25 Uc operational |
Connections - terminals | Spring terminals 2 cable(s) 1...2.5 mm² - cable stiffness: solid - without cable end Spring terminals 1 cable(s) 1...2.5 mm² - cable stiffness: solid - without cable end Spring terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - without cable e |
Depth | 93 mm |
Device short name | CAD |
Height | 99 mm |
Hold-in power consumption in W | 5.4 W at 20 °C |
Inrush power in W | 5.4 W at 20 °C |
Insulation resistance | > 10 MOhm |
IP degree of protection | IP2x front face conforming to VDE 0106 |
Irms rated making capacity | 250 A DC conforming to IEC 60947-5-1 140 A AC conforming to IEC 60947-5-1 |
Mechanical durability | 30 Mcycles |
Mechanical robustness | Vibrations control relay closed 4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations control relay open 2 Gn, 5...300 Hz IEC 60068-2-6 Shocks control relay closed 15 Gn for 11 ms IEC 60068-2-27 Shocks control relay open 10 Gn for 11 ms IEC 60068-2-27 |
Minimum switching current | 5 mA |
Minimum switching voltage | 17 V |
Mounting support | Plate Rail |
Non-overlap time | 1.5 ms on de-energisation (between NC and NO contact) 1.5 ms on energisation (between NC and NO contact) |
Operating altitude | 3000 m without derating in temperature |
Operating rate | 180 cyc/mn |
Operating time | 15...25 ms coil de-energisation and NC closing 47...63 ms coil energisation and NC opening 16...24 ms coil de-energisation and NO opening 53...72 ms coil energisation and NO closing |
Pole contact composition | 3 NO + 2 NC |
Product certifications | CSA UL |
Product name | TeSys CAD |
Product or component type | Control relay |
Product weight | 0.58 kg |
Protective treatment | TH conforming to IEC 60068 |
Range | TeSys |
Standards | BS 4794 EN 60947-5 IEC 60947-5-1 NF C 63-140 VDE 0660 |
Time constant | 28 ms |
Utilisation category | AC-14 AC-15 DC-13 |
Width | 45 mm |