Varenr: | GB2CS06 |
El nr: | 7522108771 |
EAN13 nr: | 3389110724844 |
Pakning: | 1stk |
 |
[Ics] rated service short-circuit breaking capacity | 25 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 110 V AC 50/60 Hz conforming to IEC 60947-2 |
[In] rated current | 1 A |
[Ue] rated operational voltage | 48 V DC 250 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-2 |
Ambient air temperature for operation | -20...60 °C |
Ambient air temperature for storage | -40...80 °C |
Breaking capacity | Icu = 50 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 Icu = 1.5 kA at 24 V DC conforming to IEC 60947-2 Icu = 50 kA at 110 V AC 50/60 Hz conforming to IEC 60947-2 Icu = 1 kA at 48 V DC conforming to IEC 60947-2 |
Circuit breaker application | Control circuit |
Connections - terminals | Connector 2 cable(s) 0.75...2.5 mm² - cable stiffness : flexible - with cable end Connector 1 cable(s) 0.75...4 mm² - cable stiffness : flexible - with cable end Connector 2 cable(s) 0.75...4 mm² - cable stiffness : solid - without cable end Connector 1 c |
Control type | Toggle |
Depth | 67 mm |
Device short name | GB2 |
Electrical durability | 8000 cycles |
Fire resistance | 960 °C conforming to IEC 60695-2-1 |
Height | 74 mm |
IP degree of protection | IP20 conforming to IEC 60529 |
Magnetic tripping current | 6 A |
Mechanical durability | 8000 cycles |
Mechanical robustness | Vibrations 5 Gn, 5...110 Hz conforming to IEC 60068-2-6 Shocks 22 Gn for 20 ms conforming to IEC 60068-2-27 |
Mounting mode | By clips |
Mounting position | Horizontal Vertical |
Mounting support | Plate Rail |
Network frequency | 50/60 Hz conforming to IEC 60947-2 |
Network type | AC DC |
Operating altitude | 3000 m |
Period | 18 months |
Poles description | 1P |
Power dissipation per pole | 1.9 W |
Product or component type | Circuit breaker |
Product weight | 0.055 kg |
Protective treatment | TC |
Quantity per set | Set of 6 |
Range of product | TeSys GB2 |
Standards | EN 60947-1 EN 60947-2 IEC 60947-1 IEC 60947-2 |
Tightening torque | 1.2 N.m - on connector |
Trip unit technology | Thermal-magnetic |
Utilisation category | DC-13 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 Category A conforming to IEC 60947-2 |
Width | 15 mm |