Navigér
Sœg

TeSys D kontaktor 3 poler(3 NO) AC-3 <= 440 V 9 A - 110 V AC


Varenr:LC1D096F7
El nr:7522406101
EAN13 nr:3389110802504
Pakning:1stk

[Icw] rated short-time withstand current140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 61 A <= 40 °C 1 min power circuit 30 A <= 40 °C 10 min power circuit 210 A <= 40 °C 1 s power circuit 105 A <= 40 °C 10 s power circuit
[Ie] rated operational current25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit 9 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
[Ith] conventional free air thermal current10 A at <= 60 °C for signalling circuit 25 A at <= 60 °C for power circuit
[Ue] rated operational voltage<= 300 V DC for power circuit <= 690 V AC 25...400 Hz for power circuit
[Ui] rated insulation voltage600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for power circuit certifications UL 600 V for power circuit certifications CSA 690 V for power circ
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeType mirror contact (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Average impedance2.5 mOhm at 50 Hz - Ith 25 A for power circuit
Coil technologyWithout built-in suppressor module
Associated fuse rating20 A gG at <= 690 V coordination type 2 for power circuit 25 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
Connections - terminalsPower circuit : lugs-ring terminals - external diameter: 8 mm Control circuit : lugs-ring terminals - external diameter: 8 mm
Contactor applicationMotor control Resistive load
Control circuit typeAC 50/60 Hz
Control circuit voltage110 V AC 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc at 60 °C operational 60 Hz 0.8...1.1 Uc at 60 °C operational 50 Hz 0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
Depth86 mm
Device short nameLC1D
Electrical durability2 Mcycles 9 A AC-3 at Ue <= 440 V 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation2...3 W at 50/60 Hz
Height77 mm
Hold-in power consumption in VA7 VA at 20 °C (cos ? 0.3) 50 Hz 7.5 VA at 20 °C (cos ? 0.3) 60 Hz
Inrush power in VA70 VA at 20 °C (cos ? 0.75) 50 Hz 70 VA at 20 °C (cos ? 0.75) 60 Hz
Insulation resistance> 10 MOhm for signalling circuit
IP degree of protectionIP2x front face conforming to IEC 60529
Irms rated making capacity250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A at 440 V for power circuit conforming to IEC 60947
Mechanical durability15 Mcycles
Mechanical robustnessShocks contactor closed 15 Gn for 11 ms Shocks contactor open 10 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
Motor power HP (UL / CSA)7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 0.5
Motor power kW5.5 kW at 660...690 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz 4 kW at 415...440 V AC 50/60 Hz 4 kW at 380...400 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz
Mounting supportPlate Rail
Non-overlap time1.5 ms on energisation (between NC and NO contact) 1.5 ms on de-energisation (between NC and NO contact)
Operating altitude3000 m without derating in temperature
Operating rate3600 cyc/h at <= 60 °C
Operating time4...19 ms opening 12...22 ms closing
Overvoltage categoryIII
Permissible ambient air temperature around the device-40...70 °C at Uc
Poles description3P
Pollution degree3
Power dissipation per pole0.2 W AC-3 1.56 W AC-1
Power pole contact composition3 NO
Product certificationsBV CCC CSA DNV GL GOST RINA UL LROS
Product nameTeSys D
Product or component typeContactor
Product weight0.32 kg
Protective treatmentTH conforming to IEC 60068-2-30
RangeTeSys
Rated breaking capacity250 A at 440 V for power circuit conforming to IEC 60947
Safety coverWith
Signalling circuit frequency25...400 Hz
StandardsEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Utilisation categoryAC-1 AC-3
Safety reliability levelB10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Tightening torquePower circuit : 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 screw : M3.5 Power circuit : 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 8 mm screw : M3.5 Control circuit : 1.7 N.m - on lugs-ring terminals - with screwdrive
Width45 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025