Navigér
Sœg

TeSys D kontaktor 3 polet(3 NO) AC-3 <= 440 V 115 A - 230 V AC kul


Varenr:LC1D1156P7
El nr:7522407142
EAN13 nr:3389110381375
Pakning:1stk

[Icw] rated short-time withstand current140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 1100 A <= 40 °C 1 s power circuit 950 A <= 40 °C 10 s power circuit 550 A <= 40 °C 1 min power circuit 250 A <= 40 °C 10 min power circuit
[Ie] rated operational current115 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit 200 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current200 A at <= 60 °C for power circuit
[Ue] rated operational voltage<= 300 V DC for power circuit <= 1000 V AC 25...400 Hz for power circuit
[Ui] rated insulation voltage600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 1000 V for power circuit conforming to IEC 60947-4-1 600 V for power circuit certifications UL 600 V for
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Associated fuse rating10 A gG for signalling circuit 200 A gG at <= 690 V coordination type 2 for power circuit 250 A gG at <= 690 V coordination type 1 for power circuit
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeType mirror contact (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Average impedance0.6 mOhm at 50 Hz - Ith 200 A for power circuit
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Connections - terminalsPower circuit : bars 1 5 x 25 mm Power circuit : lugs-ring terminals - external diameter: 25 mm Control circuit : lugs-ring terminals - external diameter: 8 mm
Contactor applicationMotor control Resistive load
Control circuit typeAC 50/60 Hz
Control circuit voltage230 V AC 50/60 Hz
Control circuit voltage limits0.8...1.15 Uc at 55 °C operational 50/60 Hz 0.3...0.5 Uc at 55 °C drop-out 50/60 Hz
Depth136 mm
Device short nameLC1D
Electrical durability0.95 Mcycles 115 A AC-3 at Ue <= 440 V 0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation3...8 W at 50/60 Hz
Height158 mm
Hold-in power consumption in VA2...18 VA at 20 °C (cos ? 0.3) 50 Hz 2...18 VA at 20 °C (cos ? 0.3) 60 Hz
Inrush power in VA280...350 VA at 20 °C (cos ? 0.8) 50 Hz 280...350 VA at 20 °C (cos ? 0.8) 60 Hz
Insulation resistance> 10 MOhm for signalling circuit
IP degree of protectionIP2x front face conforming to IEC 60529
Irms rated making capacity250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1 1260 A at 440 V for power circuit conforming to IEC 60947
Mechanical durability8 Mcycles
Mechanical robustnessShocks contactor open 6 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
Motor power HP (UL / CSA)100 hp at 575/600 V AC 50/60 Hz for 3 phases motors 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Motor power kW65 kW at 1000 V AC 50/60 Hz 80 kW at 660...690 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 59 kW at 415...440 V AC 50/60 Hz 55 kW at 380...400 V AC 50/60 Hz 30 kW at 220...230 V AC 50/60 Hz
Mounting supportPlate Rail
Non-overlap time1.5 ms on energisation (between NC and NO contact) 1.5 ms on de-energisation (between NC and NO contact)
Operating altitude3000 m without derating in temperature
Operating rate2400 cyc/h at <= 60 °C
Operating time20...50 ms closing 6...20 ms opening
Overvoltage categoryIII
Permissible ambient air temperature around the device-40...70 °C at Uc
Poles description3P
Pollution degree3
Power dissipation per pole7.9 W AC-3 24 W AC-1
Power pole contact composition3 NO
Product certificationsBV CCC CSA DNV GL GOST RINA UL LROS
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product nameTeSys D
Product or component typeContactor
Product weight2.5 kg
Protective treatmentTH conforming to IEC 60068-2-30
RangeTeSys
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
REAChReference not containing SVHC above the threshold
RoHSCompliant - since 0932 -  Schneider Electric declaration of conformity
Safety coverWith
Signalling circuit frequency25...400 Hz
StandardsEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Utilisation categoryAC-1 AC-3
Width120 mm
Safety reliability levelB10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Tightening torquePower circuit : 12 N.m - on bars hexagonal 13 mm screw : M8 Power circuit : 12 N.m - on lugs-ring terminals hexagonal 13 mm screw : M8 Control circuit : 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 screw : M3.5 Control circuit : 1.2 N.

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info