Navigér
Sœg

TeSys D kontaktor 3 poler(3 NO) AC-3 <= 440 V 150 A - 440 V AC


Varenr:LC1D150R7
El nr:7522408125
EAN13 nr:3389110477672
Pakning:1stk

[Icw] rated short-time withstand current140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 1400 A <= 40 °C 1 s power circuit 1200 A <= 40 °C 10 s power circuit 580 A <= 40 °C 1 min power circuit 250 A <= 40 °C 10 min power circuit
[Ie] rated operational current150 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit 200 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current200 A at <= 60 °C for power circuit
[Ue] rated operational voltage<= 300 V DC for power circuit <= 1000 V AC 25...400 Hz for power circuit
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeType mirror contact (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Average impedance0.6 mOhm at 50 Hz - Ith 200 A for power circuit
[Ui] rated insulation voltage600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 1000 V for power circuit conforming to IEC 60947-4-1 600 V for power circuit certifications UL 600 V for
Associated fuse rating250 A gG at <= 690 V coordination type 2 for power circuit 315 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Connections - terminalsPower circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: solid - without cable end Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: solid - without cable end Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness
Contactor applicationMotor control Resistive load
Control circuit typeAC 50/60 Hz
Control circuit voltage440 V AC 50/60 Hz
Control circuit voltage limits0.8...1.15 Uc at 55 °C operational 50/60 Hz 0.3...0.5 Uc at 55 °C drop-out 50/60 Hz
Depth136 mm
Device short nameLC1D
Electrical durability1 Mcycles 200 A AC-1 at Ue <= 440 V 0.85 Mcycles 150 A AC-3 at Ue <= 440 V
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation3...4.5 W at 50/60 Hz
Height158 mm
Hold-in power consumption in VA2...18 VA at 20 °C (cos ? 0.9) 50 Hz 2...18 VA at 20 °C (cos ? 0.9) 60 Hz
Inrush power in VA280...350 VA at 20 °C (cos ? 0.9) 50 Hz 280...350 VA at 20 °C (cos ? 0.9) 60 Hz
Insulation resistance> 10 MOhm for signalling circuit
IP degree of protectionIP2x front face conforming to IEC 60529
Irms rated making capacity1660 A at 440 V for power circuit conforming to IEC 60947 250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1
Mechanical durability8 Mcycles
Mechanical robustnessShocks contactor open 6 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
Motor power HP (UL / CSA)125 hp at 575/600 V AC 50/60 Hz for 3 phases motors 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Motor power kW75 kW at 1000 V AC 50/60 Hz 100 kW at 660...690 V AC 50/60 Hz 90 kW at 500 V AC 50/60 Hz 80 kW at 415...440 V AC 50/60 Hz 75 kW at 380...400 V AC 50/60 Hz 40 kW at 220...230 V AC 50/60 Hz
Mounting supportPlate Rail
Non-overlap time1.5 ms on energisation (between NC and NO contact) 1.5 ms on de-energisation (between NC and NO contact)
Operating altitude3000 m without derating in temperature
Operating rate1200 cyc/h at <= 60 °C
Operating time40...75 ms opening 20...35 ms closing
Overvoltage categoryIII
Permissible ambient air temperature around the device-40...70 °C at Uc
Poles description3P
Pollution degree3
Power dissipation per pole13.5 W AC-3 24 W AC-1
Power pole contact composition3 NO
Product certificationsBV CCC CSA DNV GL GOST RINA UL LROS
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Product nameTeSys D
Product or component typeContactor
Product weight2.5 kg
Protective treatmentTH conforming to IEC 60068-2-30
RangeTeSys
Rated breaking capacity1400 A at 440 V for power circuit conforming to IEC 60947
REAChReference not containing SVHC above the threshold
RoHSCompliant - since 0927 -  Schneider Electric declaration of conformity
Safety coverWith
Safety reliability levelB10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Signalling circuit frequency25...400 Hz
StandardsEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Tightening torquePower circuit : 12 N.m - on connector hexagonal 4 mm Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Utilisation categoryAC-1 AC-3
Width120 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info