 |
[Icw] rated short-time withstand current | 140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 310 A <= 40 °C 10 s power circuit 150 A <= 40 °C 1 min power circuit 430 A <= 40 °C 1 s power circuit 60 A <= 40 °C 10 min power circuit |
[Ie] rated operational current | 38 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit 50 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit |
[Ith] conventional free air thermal current | 50 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit |
[Ue] rated operational voltage | <= 300 V DC for power circuit <= 690 V AC 25...400 Hz for power circuit |
[Ui] rated insulation voltage | 690 V for power circuit conforming to IEC 60947-4-1 600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for power circuit certifications UL 600 V for p |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
Ambient air temperature for operation | -5...60 °C |
Ambient air temperature for storage | -60...80 °C |
Associated fuse rating | 63 A gG at <= 690 V coordination type 2 for power circuit 63 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1 |
Auxiliary contact composition | 1 NO + 1 NC |
Auxiliary contacts type | Type mirror contact (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1 |
Average impedance | 2 mOhm at 50 Hz - Ith 50 A for power circuit |
Coil technology | Built-in bidirectional peak limiting diode suppressor |
Connections - terminals | Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 1 cable(s) 1.5...10 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 2 c |
Contactor application | Motor control Resistive load |
Control circuit type | DC standard |
Control circuit voltage | 110 V DC |
Control circuit voltage limits | 0.7...1.25 Uc at 60 °C operational 0.1...0.25 Uc at 60 °C drop-out |
Depth | 101 mm |
Device short name | LC1D |
Electrical durability | 1.4 Mcycles 38 A AC-3 at Ue <= 440 V 1.4 Mcycles 50 A AC-1 at Ue <= 440 V |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Flame retardance | V1 conforming to UL 94 |
Height | 85 mm |
Hold-in power consumption in W | 5.4 W at 20 °C |
Inrush power in W | 5.4 W at 20 °C |
Insulation resistance | > 10 MOhm for signalling circuit |
IP degree of protection | IP2x front face conforming to IEC 60529 |
Irms rated making capacity | 550 A at 440 V for power circuit conforming to IEC 60947 250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1 |
Mechanical durability | 30 Mcycles |
Mechanical robustness | Shocks contactor open 8 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz |
Minimum switching current | 5 mA for signalling circuit |
Minimum switching voltage | 17 V for signalling circuit |
Motor power HP (UL / CSA) | 25 hp at 600 V AC 50/60 Hz for 3 phases motors 20 hp at 480 V AC 50/60 Hz for 3 phases motors 5 hp at 240 V AC 50/60 Hz for 1 phase motors 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors |
Motor power kW | 18.5 kW at 415...440 V AC 50/60 Hz 9 kW at 220...230 V AC 50/60 Hz 18.5 kW at 660...690 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 18.5 kW at 380...400 V AC 50/60 Hz |
Mounting support | Plate Rail |
Non-overlap time | 1.5 ms on energisation (between NC and NO contact) 1.5 ms on de-energisation (between NC and NO contact) |
Operating altitude | 3000 m without derating in temperature |
Operating rate | 3600 cyc/h at <= 60 °C |
Operating time | 53.55...72.45 ms closing 16...24 ms opening |
Overvoltage category | III |
Permissible ambient air temperature around the device | -40...70 °C at Uc |
Poles description | 3P |
Pollution degree | 3 |
Power dissipation per pole | 3 W AC-3 5 W AC-1 |
Power pole contact composition | 3 NO |
Product certifications | BV CCC CSA DNV GL GOST RINA UL LROS |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product name | TeSys D |
Product or component type | Contactor |
Product weight | 0.54 kg |
Protective treatment | TH conforming to IEC 60068-2-30 |
Range | TeSys |
Rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
REACh | Reference not containing SVHC above the threshold |
RoHS | Compliant - since 0627 - Schneider Electric declaration of conformity |
Safety cover | With |
Safety reliability level | B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 |
Signalling circuit frequency | 25...400 Hz |
Standards | EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
Sustainable offer status | Green Premium product |
Tightening torque | Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Contr |
Time constant | 28 ms |
Utilisation category | AC-1 AC-3 |
Width | 45 mm |