[Icw] rated short-time withstand current | 320 A <= 40 °C 1 min power circuit 135 A <= 40 °C 10 min power circuit 990 A <= 40 °C 1 s power circuit 640 A <= 40 °C 10 s power circuit |
[Ie] rated operational current | 125 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit |
[Ith] conventional free air thermal current | 125 A at <= 60 °C for power circuit |
[Ue] rated operational voltage | <= 690 V AC for power circuit <= 300 V DC 25...400 Hz for power circuit |
[Ui] rated insulation voltage | 1000 V for power circuit conforming to IEC 60947-4-1 600 V for power circuit certifications UL 600 V for power circuit certifications CSA |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
Ambient air temperature for operation | -5...60 °C |
Ambient air temperature for storage | -60...80 °C |
Associated fuse rating | 160 A gG at <= 690 V coordination type 2 for power circuit 200 A gG at <= 690 V coordination type 1 for power circuit |
Average impedance | 0.8 mOhm at 50 Hz - Ith 125 A for power circuit |
Coil technology | Without built-in suppressor module |
Connections - terminals | Power circuit : connector 2 cable(s) 4...25 mm² - cable stiffness: solid - without cable end Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: solid - without cable end Power circuit : connector 2 cable(s) 4...16 mm² - cable stiffness: fl |
Contactor application | Resistive load |
Control circuit type | AC 50/60 Hz |
Control circuit voltage | 24 V AC 50/60 Hz |
Control circuit voltage limits | 0.85...1.1 Uc at 55 °C operational 60 Hz 0.8...1.1 Uc at 55 °C operational 50 Hz 0.3...0.6 Uc at 55 °C drop-out 50/60 Hz |
Depth | 125 mm |
Device short name | LC1D |
Electrical durability | 0.8 Mcycles 125 A AC-1 at Ue <= 440 V |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Flame retardance | V1 conforming to UL 94 |
Heat dissipation | 6...10 W at 50/60 Hz |
Height | 127 mm |
Hold-in power consumption in VA | 26 VA at 20 °C (cos ? 0.3) 50 Hz 26 VA at 20 °C (cos ? 0.3) 60 Hz |
Inrush power in VA | 245 VA at 20 °C (cos ? 0.75) 50 Hz 245 VA at 20 °C (cos ? 0.75) 60 Hz |
IP degree of protection | IP2x front face conforming to IEC 60529 |
Irms rated making capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
Mechanical durability | 4 Mcycles |
Mechanical robustness | Shocks contactor closed 10 Gn for 11 ms Vibrations contactor closed 3 Gn, 5...300 Hz Shocks contactor open 8 Gn for 11 ms Vibrations contactor open 2 Gn, 5...300 Hz |
Mounting support | Plate Rail |
Operating altitude | 3000 m without derating in temperature |
Operating rate | 3600 cyc/h at <= 60 °C |
Operating time | 6...20 ms opening 20...35 ms closing |
Overvoltage category | III |
Permissible ambient air temperature around the device | -40...70 °C at Uc |
Poles description | 4P |
Pollution degree | 3 |
Power dissipation per pole | 12.5 W AC-1 |
Power pole contact composition | 4 NO |
Product certifications | BV CCC CSA DNV GL GOST RINA UL LROS |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product name | TeSys D |
Product or component type | Contactor |
Product weight | 1.76 kg |
Protective treatment | TH conforming to IEC 60068-2-30 |
Range | TeSys |
Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
REACh | Reference not containing SVHC above the threshold |
RoHS | Compliant - since 0701 - Schneider Electric declaration of conformity |
Safety cover | Without |
Safety reliability level | B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 |
Standards | EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
Sustainable offer status | Green Premium product |
Tightening torque | Power circuit : 9 N.m - on connector hexagonal 4 mm Power circuit : 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit : 1.2 N.m - on screw clamp |
Utilisation category | AC-1 |
Width | 96 mm |