[Icw] rated short-time withstand current | 3000 A <= 40 °C 10 min 4200 A <= 40 °C 3 min 5500 A <= 40 °C 1 min 7500 A <= 40 °C 30 s 10000 A <= 40 °C 10 s power circuit |
[Ie] rated operational current | 2100 A (<= 40 °C) at <= 440 V AC AC-1 |
[Ith] conventional free air thermal current | 2100 A at <= 40 °C |
[Ue] rated operational voltage | <= 460 V DC <= 1000 V AC 50/60 Hz |
[Ui] rated insulation voltage | 1500 V conforming to VDE 0110 group C 1000 V conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 8 kV |
Ambient air temperature for operation | -5...40 °C |
Ambient air temperature for storage | -60...80 °C |
Associated fuse rating | 2000 A gG at <= 440 V for power circuit conforming to IEC 60947-4-1 |
Average impedance | 0.1 mOhm at 50 Hz - Ith 2100 A |
Connections - terminals | Power circuit : bar 4 Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : scr |
Contactor application | Resistive load |
Depth | 238.6 mm |
Device short name | LC1F |
Height | 332 mm |
Irms rated making capacity | 3150 A AC conforming to IEC 60947-4-1 |
Mechanical robustness | Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor open 6 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms Vibrations contactor open 2 Gn, 5...300 Hz |
Mounting support | Plate |
Operating altitude | 3000 m without derating in temperature |
Overvoltage category | III |
Permissible ambient air temperature around the device | -40...60 °C |
Poles description | 3P |
Power dissipation per pole | 200 W AC-1 |
Power pole contact composition | 3 NO |
Product certifications | CCC CSA UL/ETL verified |
Product environmental profile | Available Download Product environmental |
Product name | TeSys F |
Product or component type | Contactor |
Product weight | 31 kg |
Protective treatment | TH |
Range | TeSys |
Rated breaking capacity | 3150 kA for power circuit conforming to IEC 60947-4-1 |
REACh | Reference not containing SVHC above the threshold |
RoHS | Compliant - since 0927 - Schneider Electric declaration of conformity |
Standards | EN 60947-1 EN 60947-4-1 IEC 60947-1 IEC 60947-4-1 JEM 1038 |
Sustainable offer status | Not Green Premium product |
Tightening torque | Power circuit : 58 N.m Control circuit : 1.2 N.m |
Utilisation category | AC-1 |
Width | 438 mm |