TeSys D kontaktor til reversering 3 poler(3 NO) AC-3 <= 440 V 9 A - 24 V AC


Varenr:LC2D09B7
El nr:7522412726
EAN13 nr:3389110383201
Pakning:1stk

[Ie] rated operational current25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit 9 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
[Ith] conventional free air thermal current25 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
[Ue] rated operational voltage<= 300 V DC for power circuit <= 690 V AC 25...400 Hz for power circuit
[Icw] rated short-time withstand current140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 210 A <= 40 °C 1 s power circuit 105 A <= 40 °C 10 s power circuit 61 A <= 40 °C 1 min power circuit 30 A <= 40 °C 10 min power circuit
[Ui] rated insulation voltage600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for power circuit certifications UL 600 V for power circuit certifications CSA 690 V for power circ
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1 20 A gG at <= 690 V coordination type 2 for power circuit 25 A gG at <= 690 V coordination type 1 for power circuit
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeType mirror contact (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Average impedance2.5 mOhm at 50 Hz - Ith 25 A for power circuit
Coil technologyWithout built-in suppressor module
Connections - terminalsControl circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 c
Contactor applicationMotor control Resistive load
Control circuit typeAC 50/60 Hz
Control circuit voltage24 V AC 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc at 60 °C operational 60 Hz 0.8...1.1 Uc at 60 °C operational 50 Hz 0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
Depth86 mm
Device presentationPreassembled with reversing power busbar
Device short nameLC2D
Electrical durability2 Mcycles 9 A AC-3 at Ue <= 440 V 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation2...3 W at 50/60 Hz
Height77 mm
Hold-in power consumption in VA7 VA at 20 °C (cos ? 0.3) 50 Hz 7.5 VA at 20 °C (cos ? 0.3) 60 Hz
Inrush power in VA70 VA at 20 °C (cos ? 0.75) 50 Hz 70 VA at 20 °C (cos ? 0.75) 60 Hz
Insulation resistance> 10 MOhm for signalling circuit
Interlocking typeMechanical
IP degree of protectionIP2x front face conforming to IEC 60529
Irms rated making capacity250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A at 440 V for power circuit conforming to IEC 60947
Mechanical durability15 Mcycles
Mechanical robustnessShocks contactor closed 15 Gn for 11 ms Shocks contactor open 10 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
Minimum switching current5 mA for signalling circuit
Motor power kW5.5 kW at 660...690 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz 4 kW at 415...440 V AC 50/60 Hz 4 kW at 380...400 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz
Mounting supportPlate Rail
Non-overlap time1.5 ms on energisation (between NC and NO contact) 1.5 ms on de-energisation (between NC and NO contact)
Operating altitude3000 m without derating in temperature
Operating rate3600 cyc/h at <= 60 °C
Motor power HP (UL / CSA)7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 0.5
Operating time4...19 ms opening 12...22 ms closing
Overvoltage categoryIII
Permissible ambient air temperature around the device-40...70 °C at Uc
Poles description3P
Pollution degree3
Power dissipation per pole1.56 W AC-1 0.2 W AC-3
Power pole contact composition3 NO
Product certificationsBV CCC CSA DNV GL GOST RINA UL LROS
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Product nameTeSys D
Product or component typeReversing contactor
Product weight0.687 kg
Protective treatmentTH conforming to IEC 60068-2-30
RangeTeSys
Rated breaking capacity250 A at 440 V for power circuit conforming to IEC 60947
REAChReference not containing SVHC above the threshold
RoHSCompliant - since 0627 -  Schneider Electric declaration of conformity
Safety coverWith
Safety reliability levelB10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Signalling circuit frequency25...400 Hz
StandardsEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Tightening torqueControl circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Pow
Utilisation categoryAC-1 AC-3
Width90 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025