Navigér
Sœg

TeSys D kontaktor til reversering 3 poler(3 NO) AC-3 <= 440 V 115 A-120 V AC


Varenr:LC2D115G7
El nr:7522413741
EAN13 nr:3389110531510
Pakning:1stk

[Ie] rated operational current115 A (<= 60 °C) at <= 440 V AC AC-3 for effekt kreds 200 A (<= 60 °C) at <= 440 V AC AC-1 for effekt kreds
[Ie] rated operational current115 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit 200 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current200 A at <= 60 °C for effekt kreds
[Ith] conventional free air thermal current200 A at <= 60 °C for power circuit
[Ue] rated operational voltage<= 1000 V AC 25...400 Hz for effekt kreds <= 690 V DC effekt kreds
[Icw] rated short-time withstand current1100 A <= 40 °C 1 s effekt kreds 950 A <= 40 °C 10 s effekt kreds 550 A <= 40 °C 1 min effekt kreds 250 A <= 40 °C 10 min effekt kreds 140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit
[Icw] rated short-time withstand current1100 A <= 40 °C 1 s power circuit 950 A <= 40 °C 10 s power circuit 550 A <= 40 °C 1 min power circuit 250 A <= 40 °C 10 min power circuit 140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit
[Ue] rated operational voltage<= 300 V DC for power circuit <= 1000 V AC 25...400 Hz for power circuit
[Ui] rated insulation voltage1000 V for effekt kreds conforming to IEC 60947-4-1 600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for effekt kreds certifications UL 600 V for ef
[Ui] rated insulation voltage1000 V for power circuit conforming to IEC 60947-4-1 600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for power circuit certifications UL 600 V for
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
AflasningstypeElektrisk Mekanisk
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Arbejdsforhold2400 cyc/h at <= 60 °C
Associated fuse rating200 A gG at <= 690 V coordination type 2 for power circuit 250 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeType mirror contact (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Average impedanceAt 50 Hz - Ith 200 A for power circuit
BeskyttelsesbehandlingTH conforming to IEC 60068-2-30
BeskyttelsesdækselMed
Brandmodstand850 °C conforming to IEC 60695-2-1
Bredde266 mm
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Coil technologyWithout built-in suppressor module
Connections - terminalsPower circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: solid - without cable end Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: solid - without cable end Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness
Contactor applicationMotor control Resistive load
Control circuit typeAC 50/60 Hz
Control circuit voltage120 V AC 50/60 Hz
Control circuit voltage limits0.8...1.15 Uc at 55 °C operational 50/60 Hz 0.3...0.5 Uc at 55 °C drop-out 50/60 Hz
Depth148 mm
Device presentationPreassembled with reversing power busbar
Device short nameLC2D
Driftshøjde3000 m uden derating in temperature
Driftstid6...20 ms åben 20...50 ms closing
Dybde148 mm
Effekttab i pr. polAC-3 AC-1
Electrical durability0.95 Mcycles 115 A AC-3 at Ue <= 440 V 0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Elektrisk holdbarhed0.95 Mcycles 115 A AC-3 at Ue <= 440 V 0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Enhedens korte navnLC2D
Enhedens udseendePreassembled with reversing power busbar
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
FlammemodstandV1 conforming to UL 94
Forureningsgrad3
Heat dissipation3...8 W at 50/60 Hz
Height158 mm
HjælpekontakttypeType intern kontakt (1 NC) conforming to IEC 60947-4-1 Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Hold-in power consumption in VA2...18 VA at 20 °C (cos ? 0.3) 50 Hz 2...18 VA at 20 °C (cos ? 0.3) 60 Hz
Højde158 mm
Impedans0.6 mOhm at 50 Hz - Ith 200 A for effekt kreds
Indkoblingseffekt i VA280...350 VA at 20 °C (cos ? 0.8) 50 Hz 280...350 VA at 20 °C (cos ? 0.8) 60 Hz
Ingen overlappende tid1.5 ms på energien (between NC and NO contact) 1.5 ms på de-energinisering (between NC and NO contact)
Inrush power in VA280...350 VA at 20 °C (cos ? 0.8) 50 Hz 280...350 VA at 20 °C (cos ? 0.8) 60 Hz
Insulation resistance> 10 MOhm for signalling circuit
Interlocking typeElectrical Mechanical
IP degree of protectionIP2x front face conforming to IEC 60529
IP kapslingsklasseIP2x fronten IEC 60529
Irms rated making capacity1260 A at 440 V for power circuit conforming to IEC 60947 250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1
Isolationsmodstand> 10 MOhm for signalling circuit
Mechanical durability8000000 cycles
Mechanical robustnessShocks contactor open 6 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
Mekanisk holdbarhed8000000 cycles
Minimum sluttestrøm5 mA for signalling circuit
Minimum spænding17 V for signalling circuit
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
MontagevejledningPlade Skinne
Motor power HP (UL / CSA)100 hp at 575/600 V AC 50/60 Hz for 3 phases motors 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Motor power kW65 kW at 1000 V AC 50/60 Hz 80 kW at 660...690 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 59 kW at 415...440 V AC 50/60 Hz 55 kW at 380...400 V AC 50/60 Hz 30 kW at 220...230 V AC 50/60 Hz
Motoreffekt i hp100 hp 575/600 V AC 50/60 Hz 3 faser 75 hp 460/480 V AC 50/60 Hz 3 faser 40 hp 230/240 V AC 50/60 Hz 3 faser 30 hp 200/208 V AC 50/60 Hz 3 faser
Motoreffekt i kW65 KW at 1000 V AC 50/60 Hz 80 KW at 660...690 V AC 50/60 Hz 75 KW at 500 V AC 50/60 Hz 59 KW at 415...440 V AC 50/60 Hz 55 KW at 380...400 V AC 50/60 Hz 30 KW at 220...230 V AC 50/60 Hz
Mounting supportPlate Rail
Mærkebrydeevne1100 A at 440 V for effekt kreds conforming to IEC 60947
Non-overlap time1.5 ms on energisation (between NC and NO contact) 1.5 ms on de-energisation (between NC and NO contact)
Operating altitude3000 m without derating in temperature
Operating rate2400 cyc/h at <= 60 °C
Operating time6...20 ms opening 20...50 ms closing
OverspændingskategoriIII
Overvoltage categoryIII
Permissible ambient air temperature around the device-40...70 °C at Uc
Polbeskrivelse3P
Mærkeslutteevne Irms1260 A at 440 V for effekt kreds conforming to IEC 60947 250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1
Pole contact composition3 NO
Poles description3P
Pollution degree3
Power dissipation per pole7.9 W AC-3 24 W AC-1
Power pole contact composition3 NO
Product certificationsBV CCC CSA DNV GL GOST RINA UL LROS
Product nameTeSys D
Product or component typeReversing contactor
Product weight6.35 kg
ProductcertificeringerBV CCC CSA DNV GL GOST RINA UL LROS
ProdukttypeReversibel kontaktor
Protective treatmentTH conforming to IEC 60068-2-30
RangeTeSys
Range of productTeSys d
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
Safety coverWith
Safety reliability levelB10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Signalling circuit frequency25...400 Hz
StandarderEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 n°14
StandardsEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Strømvarmetab3...8 W at 50/60 Hz
Styrekredsens spændingsgrænser0.8...1.15 Uc at 55 °C operational 50/60 Hz 0.3...0.5 Uc at 55 °C drop-out 50/60 Hz
Styrespænding120 V AC 50/60 Hz
Tightening torquePower circuit : 12 N.m - on connector hexagonal 4 mm Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Til kobling afMotor kontrol Resistive load
Tilhørende sikringsstørrelse200 A gG at <= 690 V coordination type 2 for effekt kreds 250 A gG at <= 690 V coordination type 1 for effekt kreds 10 A gG for signalling circuit conforming to IEC 60947-5-1
Tilladelig omgivelsestemperatur omkring enheden-40...70 °C at Uc
TilslutningsklemmerPower circuit: connector 2 cable(s) 10...50 mm² - cable stiffness: solid - without cable end Power circuit: connector 1 cable(s) 10...120 mm² - cable stiffness: solid - without cable end Power circuit: connector 2 cable(s) 10...50 mm² - cable stiffness: f
TilspændingsmomentEffekt kreds: 12 N.m - on connector hexagonal 4 mm Control circuit: 1.2 N.m - on skrue klemmeterminaler - with screwdriver Philips No 2 Control circuit: 1.2 N.m - on skrue klemmeterminaler - with screwdriver flat Ø 6 mm
Utilisation categoryAC-1 AC-3
Vægt6.35 kg
Width266 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025