[Ith] conventional free air thermal current | 5 A for output control relay |
[Uc] control circuit voltage | 24 V DC |
[Ue] rated operational voltage | 415 V |
[Ui] rated insulation voltage | 1500 V AC 50/60 Hz 60 s between output and earth or between output and internal logic |
AS-interface profile | 7.D.F.F standard addressing 7.A.7.0 extended adressing A/B |
Contactor application | Motor control |
Control circuit voltage limits | 250 V for AC circuit output control relay 30 V for DC circuit |
Control type | Rotary knob blue Rotary knob black |
Depth | 175 mm |
Device short name | LF4P |
Electrical durability | 800000 cycles automatic operation 100000 cycles manual operation |
Enclosure material | Polycarbonate impregnated glass fiber |
Breaking capacity | Icu > 100 kA at 400...415 V conforming to IEC 60947-2 Icu > 100 kA at 230...240 V conforming to IEC 60947-2 Ics > 100 kA at 400...415 V conforming to IEC 60947-2 Ics > 100 kA at 230...240 V conforming to IEC 60947-2 |
Connections - terminals | Power supply: screw clamp terminals 2 cable <= 6 mm² - cable stiffness: solid Power supply: screw clamp terminals 2 cable <= 6 mm² - cable stiffness: flexible - without cable end Power supply: screw clamp terminals 2 cable <= 4 mm² - cable stiffness: flex |
Current consumption | 30 mA at 24 V DC for auxiliary supply energisation 20 mA for AS-Interface line sealed 20 mA for AS-Interface line relays 20 mA for AS-Interface line inrush 20 mA for AS-Interface line de-energisation 110 mA at 24 V DC for auxiliary supply inrush 0 mA at 2 |
Fire resistance | 960 °C conforming to IEC 60695-2-1 |
Height | 195 mm |
Input current | > 6 mA state 1 > 2 mA state 0 |
Input description | Status D3 (0) sensor 2 Status D2 (0) sensor 1 Status D1 (0) running Status D0 (0) ready |
Input voltage | > 11 V DC state 1 < 5 V DC state 0 |
IP degree of protection | IP54 conforming to IEC 60529 |
Maximum sensor supply current | 50 mA |
Mechanical durability | 5000000 cycles automatic operation 100000 cycles manual operation |
Motor power kW | 0.25 kW at 400...415 V AC 50/60 Hz 0.12 kW at 220...230 V AC 50/60 Hz 0.09 kW at 220...230 V AC 50/60 Hz |
Motor starter composition | Contactor With circuit breaker |
Motor starter type | Reversing |
Network frequency | 50/60 Hz |
Network type | AC |
Non-dissipating shock wave | 2.5 kV AS-Interface conforming to IEC 60947-1 2.5 kV 1 line/standard for sensor conforming to IEC 60947-1 2.5 kV 1 line/standard for 24 V conforming to IEC 60947-1 6 kV power conforming to IEC 60947-1 |
Number of sensors | 2 |
Operating altitude | <= 2000 m |
Output description | Command D3 (O) not used - bit value: bit value 1 Command D2 (O) control relay - bit value: bit value 1 Command D1 (O) reverse running - bit value: bit value 1 Command D0 (O) forward running - bit value: bit value 1 |
Poles description | 3P |
Product end of life instructions | Need no specific recycling operations |
Product or component type | Enclosed DOL starter |
Product weight | 1.55 kg |
Protection type | Overload protection a quick-blow fuse must be fitted DC inductive overloads by switching the coils of preactuators Against short-circuits a quick-blow fuse must be fitted AC inductive overloads by switching the coils of preactuators |
Protective treatment | TC |
Range of product | TeSys |
Resistance across terminals | > 1000 mOhm between output terminals and AS-Interface |
Resistance to electrostatic discharge | 8 kV open air conforming to IEC 61000-4-2 8 kV open air conforming to EN 61000-4-2 4 kV indirect mode conforming to IEC 61000-4-2 4 kV indirect mode conforming to EN 61000-4-2 |
Resistance to fast transients | 2 kV power conforming to IEC 61000-4-4 2 kV power conforming to EN 61000-4-4 2 kV AS-Interface conforming to IEC 61000-4-4 2 kV AS-Interface conforming to EN 61000-4-4 2 kV 24 V sensor conforming to IEC 61000-4-4 2 kV 24 V sensor conforming to EN 61000-4- |
Response time | < 15 ms unlatching for output control relay < 10 ms latching for output control relay |
RoHS | Compliant - since 0925 - Schneider Electric declaration of conformity |
Shock resistance | 15 gn contactor closed conforming to IEC 60068-2-27 10 gn contactor open conforming to IEC 60068-2-27 |
Standards | EN 60204-1 EN 60947-1 IEC 60439-1 |
Sustainable offer status | Not Green Premium product |
Resistance to radiated fields | 10 V/m immunity tests-radiated disturbances conforming to ENV 50204 10 V/m immunity tests-radiated disturbances conforming to ENV 50141 10 V/m immunity tests-radiated disturbances conforming to ENV 50140 10 V/m immunity tests-conducted disturbances confor |
Service life in cycles | 5000000 cycles at 0.25 A 24 V AC AC-14 - load type inductive - for output control relay 1000000 cycles at 0.5 A 24 V AC AC-14 - load type inductive - for output control relay > 1000000 cycles at 0.25 A 24 V DC DC-3 - load type resistive - for output contr |
Thermal protection adjustment range | 0.63...1 A |
Tightening torque | Power supply: 1.7 N.m - with screwdriver Philips No 2 Power supply: 1.7 N.m - with screwdriver flat Ø 5.5 mm Output control relay: 0.7 N.m - with screwdriver flat Ø 3.5 mm Motor: 0.8 N.m - with screwdriver Philips No 2 Motor: 0.8 N.m - with screwdriver fl |
Trip unit technology | Thermal-magnetic |
Utilisation category | AC-3 |
Vibration resistance | 4 gn 5...150 Hz contactor closed conforming to IEC 60068-2-6 2 gn 5...150 Hz contactor open conforming to IEC 60068-2-6 |
Width | 175 mm |
Wiring technique | 2-wire 3-wire |