[Ics] rated service breaking capacity | 50 kA 440 V 50 kA 230 V 4 kA 690 V 10 kA 500 V |
[Ie] rated operational current | 9 A at 690 V 12 A at 500 V 12 A at <= 440 V |
[Ith] conventional free air thermal current | 12 A |
[Ue] rated operational voltage | 690 V 500 V 440 V 230 V |
[Ui] rated insulation voltage | 600 V conforming to CSA C22.2 No 14 690 V conforming to IEC 60947-1 3 600 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
Ambient air temperature for operation | -25...70 °C with LUCA, LUCB, LUCC, LUCD -25...60 °C with LUCM |
Ambient air temperature for storage | -40...85 °C |
Auxiliary contact composition | 1 NO + 1 NC |
Auxiliary contacts type | Type mirror contact (1 NC) state of the power conforming to draft IEC 60947-1 Type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1 |
Connections - terminals | Power circuit : screw clamp terminals 2 cable 1.5...6 mm˛ - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable 1...6 mm˛ - cable stiffness: rigid - without cable end Power circuit : screw clamp terminals 2 cable 1. |
Depth | 126 mm |
Device short name | LUB |
Fire resistance | 650 °C conforming to IEC 60695-2-12 960 °C parts supporting live components conforming to IEC 60695-2-12 |
Heat dissipation | 1.7 W for control circuit with LUCM 2 W for control circuit with LUCA, LUCB, LUCC, LUCD |
Height | 145 mm |
Immunity to microbreaks | 3 ms |
Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
Immunity to voltage dips | 70 % 500 ms conforming to IEC 61000-4-11 |
Mechanical durability | 15000000 cycles |
Network frequency | 40...60 Hz |
Operating altitude | 2000 m |
Operating rate | 60 cyc/mn |
Poles description | 3P |
Product certifications | ABS ASEFA ATEX BV CCC CSA DNV GL GOST LROS (Lloyds register of shipping) UL |
Product name | TeSys U |
Product or component type | Non reversing power base |
Product weight | 0.9 kg |
Protective treatment | TH conforming to IEC 60068 |
Quantity per set | Set of 10 |
Range | TeSys |
Resistance to electrostatic discharge | 8 kV level 4 on contact conforming to IEC 61000-4-2 8 kV level 3 in open air conforming to IEC 61000-4-2 |
IP degree of protection | IP40 front panel outside connection zone conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP20 front panel and wired terminals conforming to IEC 60947-1 |
Non-dissipating shock wave | 2 kV common mode 48...220 V DC conforming to IEC 60947-6-2 2 kV common mode 24...240 V AC conforming to IEC 60947-6-2 1 kV serial mode 48...220 V DC conforming to IEC 60947-6-2 1 kV serial mode 24...240 V AC conforming to IEC 60947-6-2 |
Operating time | 75 ms closing with LUCM for control circuit 70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for control circuit 60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit 50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD for control circui |
Resistance to fast transients | 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 2 kV class 3 serial link conforming to IEC 61000-4-4 |
Resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
Safe separation of circuit | 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N |
Safety reliability level | B10d 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 B10d 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 |
Shock resistance | 15 gn power poles closed conforming to IEC 60068-2-27 10 gn power poles open conforming to IEC 60068-2-27 |
Standards | CSA C22.2 No 14 type E IEC 60947-6-2 EN 60947-6-2 UL 508 type E with phase barrier |
Suitability for isolation | Yes |
Tightening torque | Power circuit : 1.9...2.5 N.m - with screwdriver 6 mm Philips No 2 Power circuit : 1.9...2.5 N.m - with screwdriver 6 mm flat Control circuit : 0.8...1.2 N.m - with screwdriver 5 mm Philips no 1 Control circuit : 0.8...1.2 N.m - with screwdriver 5 mm flat |
Typical current consumption | 70 mA at 24 V DC I rms sealed with LUCM 70 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD 60 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 35 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 35 mA at 48...72 V AC I rms sealed w |
Utilisation category | AC-41 AC-43 AC-44 |
Vibration resistance | 4 gn 5...300 Hz power poles closed conforming to IEC 60068-2-27 2 gn 5...300 Hz power poles open conforming to IEC 60068-2-27 |
Width | 45 mm |