[Ics] rated service breaking capacity | Ics 100 kA 750 V DC conforming to IEC 60947-2 Ics 100 kA 500 V DC conforming to IEC 60947-2 Ics 100 kA 48/125 V DC conforming to IEC 60947-2 Ics 100 kA 250 V DC conforming to IEC 60947-2 |
[In] rated current | 400 A ( 40 °C ) 320 A ( 65 °C ) |
[Ue] rated operational voltage | 750 V DC conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 800 V DC conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
Ambient air temperature for operation | -25...70 °C |
Ambient air temperature for storage | -50...85 °C |
Breaking capacity code | S |
Circuit breaker application | Distribution |
Circuit breaker CT rating | 400 A |
Connection pitch | 45 mm |
Control type | Toggle |
Depth | 110 mm |
Device short name | Compact NSX400S |
Downside connection | Front |
Breaking capacity | Icu 100 kA at 750 V DC 3P conforming to IEC 60947-2 Icu 100 kA at 500 V DC 2P conforming to IEC 60947-2 Icu 100 kA at 48/125 V DC 1P conforming to IEC 60947-2 Icu 100 kA at 250 V DC 1P conforming to IEC 60947-2 |
Electrical durability | 2000 cycles 750 V DC In/2 conforming to IEC 60947-2 2000 cycles 500 V DC In/2 conforming to IEC 60947-2 2000 cycles 250 V DC In/2 conforming to IEC 60947-2 1000 cycles 750 V DC In conforming to IEC 60947-2 1000 cycles 500 V DC In conforming to IEC 60947-2 |
Height | 225 mm |
IK degree of protection | IK07 conforming to EN 50102 |
Instantaneous pick-up adjustment range | 1250...2500 A |
Instantaneous pick-up adjustment type Ii | Adjustable |
IP degree of protection | IP40 conforming to IEC 60529 |
Local signalling | Positive contact indication |
Magnetic tripping current | 1250...2500 A |
Mechanical durability | 5000 cycles |
Mounting mode | Fixed |
Mounting support | Backplate |
Network type | DC |
Neutral position | Left |
Neutral protection setting | No protection |
Poles description | 4P |
Pollution degree | 3 conforming to IEC 60947 |
Product certifications | ASEFA ASTA KEMA LCIE |
Product end of life instructions | Available Download End of life manual |
Product environmental profile | Available Download Product environmental |
Product or component type | Circuit breaker |
Protected poles description | 4t |
Protection type | Short-circuit protection (magnetic) |
Range | Compact |
REACh | Reference not containing SVHC above the threshold |
RoHS (date code: YYWW) | Compliant - since 0819 - Schneider Electric declaration of conformity |
Standards | IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Sustainable offer status | Green Premium product |
Trip unit name | MP2 |
Trip unit technology | Magnetic |
Upside connection | Front |
Utilisation category | Category A |
Width | 185 mm |