Maksimalafbryder DC NSX100S 63 A 2P


Varenr:LV438618
El nr:3322710664
EAN13 nr:3606480073953
Pakning:1stk

[Ics] rated service breaking capacityIcs 100 kA 220 V AC 50/60 Hz conforming to IEC 60947-2 Ics 100 kA 500 V DC conforming to IEC 60947-2 Ics 100 kA 48/125 V DC conforming to IEC 60947-2 Ics 100 kA 250 V DC conforming to IEC 60947-2 Ics 70 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 I
[In] rated current100 A ( 65 °C ) 100 A ( 40 °C )
[Ue] rated operational voltage500 V DC conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-50...85 °C
Breaking capacityIcu 100 kA at 220 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 35 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC 100 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC Icu 100 kA at 500 V DC 2P conformi
Breaking capacity codeS
Circuit breaker applicationDistribution
Connection pitch35 mm
Control typeToggle
Depth86 mm
Device short nameCompact NSX100S
Downside connectionFront
Electrical durability20000 cycles 277 V AC 50/60 Hz In/2 conforming to IEC 60947-2 10000 cycles 277 V AC 50/60 Hz In conforming to IEC 60947-2
Height161 mm
IK degree of protectionIK07 conforming to EN 50102
Instantaneous pick-up adjustment range500 A
Instantaneous pick-up adjustment type IiFixed
IP degree of protectionIP40 conforming to IEC 60529
Local signallingPositive contact indication
Long time pick-up adjstment type IrFixed
Long time pick-up adjustment range0.8...1 x In
Magnetic tripping current1000 A 1250 A 190 A 260 A 300 A 500 A 640 A 800 A
Mechanical durability20000 cycles
Mounting modeFixed
Mounting supportBackplate
Network frequency50/60 Hz
Network typeAC DC
Poles description2P
Pollution degree3 conforming to IEC 60947
Product certificationsASEFA ASTA KEMA LCIE
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable
Product or component typeCircuit breaker
Protected poles description2t
Protection typeOverload protection (thermal) Short-circuit protection (magnetic)
RangeCompact
REAChReference not containing SVHC above the threshold
RoHS (date code: YYWW)Compliant - since 1221 -  Schneider Electric declaration of conformity
StandardsIEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2
Sustainable offer statusGreen Premium product
Trip unit nameTM-D
Trip unit protection functionsLI
Trip unit rating63 A ( 40 °C )
Trip unit technologyThermal-magnetic
Upside connectionFront
Utilisation categoryCategory A
Width70 mm