Navigér
Sœg

Maksimalafbryder DC NSX160N 125 A 1P


Varenr:LV438679
El nr:3322710716
EAN13 nr:3606480074165
Pakning:1stk

[In] rated current160 A ( 40 °C ) 150 A ( 65 °C )
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-50...85 °C
Breaking capacity codeN
Circuit breaker applicationDistribution
[Ics] rated service breaking capacityIcs 50 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 Ics 50 kA 240 V AC 50/60 Hz conforming to UL 508 Ics 50 kA 240 V AC 50/60 Hz conforming to NEMA AB1 HIC Ics 25 kA 480 V AC 50/60 Hz conforming to UL 508 Ics 20 kA 600 V AC 50/60 Hz conforming to NE
Breaking capacityIcu 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 240 V AC 50/60 Hz conforming to UL 508 50 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC Icu 25 kA at 440 V AC 50/60 Hz conform
Connection pitch35 mm
Control typeToggle
Depth86 mm
Device short nameCompact NSX160N
Downside connectionFront
Electrical durability20000 cycles 277 V AC 50/60 Hz In/2 conforming to IEC 60947-2 10000 cycles 277 V AC 50/60 Hz In conforming to IEC 60947-2
Height161 mm
IK degree of protectionIK07 conforming to EN 50102
Instantaneous pick-up adjustment range1000 A
Instantaneous pick-up adjustment type IiFixed
IP degree of protectionIP40 conforming to IEC 60529
Local signallingPositive contact indication
Long time pick-up adjstment type IrFixed
Long time pick-up adjustment range0.8...1 x In
Mechanical durability20000 cycles
Mounting modeFixed
Mounting supportBackplate
Network frequency50/60 Hz
Network typeAC DC
Poles description1P
Pollution degree3 conforming to IEC 60947
Product certificationsASEFA ASTA KEMA LCIE
Product or component typeCircuit breaker
Protected poles description1t
Protection typeOverload protection (thermal) Short-circuit protection (magnetic)
RangeCompact
REAChReference not containing SVHC above the threshold
RoHS (date code: YYWW)Compliant - since 1221 -  Schneider Electric declaration of conformity
StandardsIEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2
Sustainable offer statusNot Green Premium product
Trip unit nameTM-D
Trip unit protection functionsLI
Trip unit rating125 A ( 40 °C )
Trip unit technologyThermal-magnetic
Upside connectionFront
Utilisation categoryCategory A
Width105 mm

Yderliger oplysninger: Se venligst SE katalog