Navigér
Sœg

Maksimalafbryder DC NSX160M 125 A 2P


Varenr:LV438709
El nr:3322710790
EAN13 nr:3606480074226
Pakning:1stk

[In] rated current160 A ( 40 °C )
[Ue] rated operational voltage500 V DC conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacityIcs 40 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 85 kA 240 V AC 50/60 Hz conforming to UL 508 Ics 35 kA 480 V AC 50/60 Hz conforming to UL 508 Ics 35 kA 480 V AC 50/60 Hz conforming to NEMA AB1 HIC Ics 20 kA 600 V AC 50/60 Hz conforming to NE
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-50...85 °C
Breaking capacityIcu 40 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC Icu 85 kA at 500 V DC 2P conforming to IEC 60947-2 85 kA at 240 V AC 50/60 Hz conformi
Breaking capacity codeM
Circuit breaker applicationDistribution
Connection pitch35 mm
Control typeToggle
Depth86 mm
Device short nameCompact NSX160M
Downside connectionFront
Electrical durability20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
Height161 mm
IK degree of protectionIK07 conforming to EN 50102
Instantaneous pick-up adjustment range1000 A
Instantaneous pick-up adjustment type IiFixed
IP degree of protectionIP40 conforming to IEC 60529
Local signallingPositive contact indication
Long time delay adjustment typeFixed
Long time pick-up adjstment type IrFixed
Long time pick-up adjustment range0.8...1 x In
Mechanical durability40000 cycles
Mounting modeFixed
Mounting supportBackplate
Network frequency50/60 Hz
Network typeAC DC
Poles description2P
Pollution degree3 conforming to IEC 60947
Product certificationsASEFA ASTA KEMA LCIE
Product or component typeCircuit breaker
Protected poles description2t
Protection typeOverload protection (thermal) Short-circuit protection (magnetic)
RangeCompact
REAChReference not containing SVHC above the threshold
RoHS (date code: YYWW)Compliant - since 1221 -  Schneider Electric declaration of conformity
StandardsIEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2
Sustainable offer statusNot Green Premium product
Trip unit nameTM-D
Trip unit protection functionsLI
Trip unit rating125 A ( 40 °C )
Trip unit technologyThermal-magnetic
Upside connectionFront
Utilisation categoryCategory A
Width105 mm