[Ie] rated operational current | <= 0.2 A at 115 V, DC-13 for 70 °C conforming to VDE 0660 <= 0.2 A at 115 V, DC-13 for 70 °C conforming to IEC 60947-5-1/1991 <= 0.1 A at 250 V, DC-13 for 70 °C conforming to VDE 0660 <= 0.1 A at 250 V, DC-13 for 70 °C conforming to IEC 60947-5-1/1991 <= |
[Ith] conventional free air thermal current | 8 A |
[Ui] rated insulation voltage | 300 V conforming to CSA 250 V conforming to IEC |
[Us] rated supply voltage | 110...240 V AC at 50/60 Hz |
Ambient air temperature for operation | -20...60 °C |
Ambient air temperature for storage | -40...85 °C |
Component name | RE8 |
Connections - terminals | Screw terminals 2 x 2.5 mm˛, flexible cable without cable end Screw terminals 2 x 1.5 mm˛, flexible cable with cable end |
Contacts material | 90/10 silver nickel contacts |
Depth | 80 mm |
Dielectric test voltage | 2.5 kV |
Discrete output type | Relay |
Disturbance radiated/conducted | CISPR 11 group 1 - class A CISPR 22 - class A |
Height | 78 mm |
Immunity to microbreaks | 3 ms |
Input compatibility | 2-wire sensors DC with leakage current < 1 mA, cable length: <= 50 m (Y1) |
Input voltage | 110...240 V (Y1) |
IP degree of protection | IP50 (casing) IP20 (terminals) |
Marking | CE |
Maximum switching current | 10 mA (Y1) |
Maximum switching voltage | 250 V |
Mechanical durability | 20000000 cycles |
Minimum pulse duration | 26 ms |
Minimum switching capacity | 10 mA at 12 V |
Non-dissipating shock wave | 4.8 kV |
Operating position | Any position without derating factor |
Overvoltage category | III conforming to IEC 60664-1 |
Pollution degree | 3 conforming to IEC 60664-1 |
Power consumption in VA | 8.5 VA at 240 V 1.8 VA at 110 V |
Product certifications | CSA GL UL |
Product or component type | Optimum industrial timing relay |
Product weight | 0.11 kg |
Range of product | Zelio Time |
Relative humidity | 15...85 % 3K3 conforming to IEC 60721-3-3 |
Repeat accuracy | < 1 % |
Reset time | 50 ms |
Resistance to electromagnetic fields | 10 V/m conforming to IEC 61000-4-3 level 3 |
Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2 level 3 6 kV in contact conforming to IEC 61000-4-2 level 3 |
Resistance to fast transients | 2 kV conforming to IEC 61000-4-4 level 3 |
Sale per indivisible quantity | 10 |
Setting accuracy of time delay | +/- 20 % of full scale |
Standards | EN/IEC 61812-1 |
Supply disconnection value | > 0.1 Uc |
Surge withstand | 2 kV conforming to IEC 61000-4-5 level 3 |
Temperature drift | < 0.2 %/°C |
Terminal description | (15-16-18)OC_ON (A1-A2)CO (Y1)UNUSED |
Tightening torque | 0.6...1.1 N.m |
Time delay range | 3...300 s |
Time delay type | C |
Vibration resistance | 0.35 mm 10...55 Hz conforming to IEC 60068-2-6 |
Voltage drift | < 2.5 %/V |
Voltage range | 0.9...1.1 Us |
Width | 22.5 mm |