[In] rated current | 5 A AC |
[Ui] rated insulation voltage | 250 V conforming to VDE 0010 250 V conforming to IEC 255 Group C |
[Us] rated supply voltage | 12 V DC |
Ambient air temperature for operation | -20...60 °C |
Ambient air temperature for storage | -40...70 °C |
Component name | REXL |
Contacts material | Cadmium free |
Contacts type and composition | 4 C/O |
Creepage distance | 4 kV/3 conforming to IEC 60664-1 |
Dielectric strength | 2 kV 1 mA/1 minute 50 Hz conforming to EN/IEC 61812-1 2 kV 1 mA/1 minute 50 Hz conforming to EN/IEC 60601-1 |
Discrete output type | Relay |
Disturbance radiated/conducted | Class B conforming to EN 55022 (EN 55011 group 1) |
Electrical durability | 100000 cycles at 250 V AC resistive |
Fixing mode | Plug-in socket |
Immunity to microbreaks | <= 5 ms |
Immunity to radioelectric fields | 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6 level 3 |
Immunity to voltage dips | 60 % / 100 ms conforming to EN/IEC 61000-4-11 30 % / 10 ms conforming to EN/IEC 61000-4-11 >= 95 % / 1 s conforming to EN/IEC 61000-4-11 |
IP degree of protection | IP50 conforming to IEC 60529 |
Local signalling | 1 LED yellow power ON 1 LED red output in operation |
Maximum power consumption | 1.5 W |
Maximum reset time | 50 ms during time delay, on de-energisation 250 ms after time delay, on de-energisation |
Maximum switching capacity | 4 x 5 A |
Maximum temporary permissible current | 10 A for < 10 s |
Mechanical durability | 10000000 cycles |
Minimum switching current | 100 mA |
Output overvoltage protection | 2 J |
Product certifications | CUL UL |
Product or component type | Miniature timing relay |
Product weight | 0.05 kg |
Range of product | Zelio Time |
Relative humidity | 95 % without condensation conforming to IEC 60068-2-6 |
Repeat accuracy | +/- 0.5 % |
Resistance to electromagnetic fields | 10 V/m conforming to EN/IEC 61000-4-3 level 3 |
Resistance to electrostatic discharge | 8 kV (in air) conforming to EN/IEC 61000-4-2 level 3 6 kV (in contact) conforming to EN/IEC 61000-4-2 level 3 |
Resistance to fast transients | 2 kV conforming to EN/IEC 61000-4-4 level 3 |
Setting accuracy of time delay | 10 % at full scale at 25 °C conforming to EN/IEC 61812-1 |
Standards | 73/23/EEC 89/336/EEC 93/68/EEC EN 50081-2 EN 61000-6-2 EN/IEC 60601-1 EN/IEC 60601-2 EN/IEC 61812-1 |
Surge withstand | 2 kV conforming to EN/IEC 61000-4-5 level 3 |
Temperature drift | 0.05 %/°C |
Time delay range | 0.1...1 h 0.1...1 min 0.1...1 s 1...10 h 1...10 min 1...10 s 10...100 h |
Time delay type | A |
Vibration resistance | 0.35 mm (f = 10...55 Hz) conforming to IEC 60068-2-6 |
Voltage drift | +/- 0.2 %/V |
Voltage range | 0.9...1.1 Us |