[Ie] rated operational current | 8 A, NC (AC-1/DC-1) conforming to IEC 16 A, NO (AC-1/DC-1) conforming to IEC |
[Ithe] conventional enclosed thermal current | 16 A at -40...40 °C |
[Ue] rated operational voltage | 88...121 V DC |
[Ui] rated insulation voltage | 400 V conforming to EN/IEC 60947 |
[Uimp] rated impulse withstand voltage | 3.6 kV conforming to IEC 61000-4-5 |
Ambient air temperature for operation | -40...85 °C (DC) -40...70 °C (AC) |
Ambient air temperature for storage | -40...85 °C |
Average coil consumption | 0.45 W DC |
Average coil resistance | 25200 Ohm (DC) at 20 °C +/- 10 % |
Contacts material | Silver alloy (Ag/Ni) |
Contacts operation | Standard |
Contacts type and composition | 1 C/O |
Control circuit voltage | 110 V DC |
Device short name | RSB |
Dielectric strength | 5000 V AC between coil and contact 2500 V AC between poles 1000 V AC between contacts |
Drop-out voltage threshold | >= 0.1 Uc DC |
Electrical durability | 100000 cycles (8 A at 250 V, AC-1) NC 100000 cycles (16 A at 250 V, AC-1) NO |
IP degree of protection | IP40 conforming to EN/IEC 60529 |
Marking | CE |
Maximum switching capacity | 448 W (DC) 4000 VA (AC) |
Maximum switching voltage | 400 V AC 300 V DC |
Mechanical durability | 30000000 cycles |
Minimum switching capacity | 300 mW at 5 mA |
Minimum switching current | 5 mA |
Minimum switching voltage | 5 V |
Operating position | Any position |
Operating rate | <= 72000 cycles/hour no-load <= 600 cycles/hour under load |
Operating time | 9 ms between coil energisation and making of the On-delay contact 4 ms between coil de-energisation and making of the Off-delay contact |
Product certifications | CSA GOST UL |
Product or component type | Plug-in relay |
Protection category | RT I |
Range of product | Zelio Relay |
Resistive rated load | 16 A at 28 V DC 16 A at 250 V AC |
Sale per indivisible quantity | 10 |
Series name | Interface relay |
Shape of pin | Flat |
Shock resistance | 5 gn for11 ms in operation conforming to EN/IEC 60068-2-27 10 gn for11 ms not operating conforming to EN/IEC 60068-2-27 |
Standards | EN/IEC 61810-1 UL 508 CSA C22.2 No 14 |
Status LED | Without |
Vibration resistance | +/- 1 mm (f = 10...55 Hz) conforming to EN/IEC 60068-2-6 |