[Us] rated supply voltage | 100...240 V AC |
Absolute accuracy error | +/- 1 % of full scale for analog input |
Ambient air temperature for operation | -10...35 °C for vertical installation -10...55 °C for horizontal installation |
Ambient air temperature for storage | -25...70 °C |
Analogue input number | 2 at input range: 0...10 V |
Analogue input resolution | 10 bits |
Backup time | 1 year at 25 °C by interruption of power supply |
Battery type | BR2032 lithium non-rechargeable, battery life: 4 yr |
Cable length | <= 30 m unshielded cable for output <= 10 m shielded cable for fast input <= 30 m unshielded cable for input |
Clock drift | <= 30 s/month at 25 °C |
Communication port protocol | Non isolated serial link : Modbus protocol master/slave - RTU/ASCII or SoMachine-Network USB port : USB protocol - SoMachine-Network |
Communication service | DHCP client Modbus TCP server Modbus TCP client Modbus TCP slave device |
Configurable filtering time | 12 ms for input 3 ms for input 0 ms for input |
Control signal type | Single phase signal at 100 kHz for fast input (HSC mode) Pulse/direction signal at 100 kHz for fast input (HSC mode) A/B signal at 50 kHz for fast input (HSC mode) |
Conversion time | 1 ms per channel + 1 controller cycle time for analog input |
Counting input number | 4 fast input (HSC mode) (counting frequency: 100 kHz), counting capacity: 32 bits |
Current per output common | 8 A |
Current state 0 guaranteed | <= 1 mA for input |
Current state 1 guaranteed | >= 2.5 mA for input |
Data backed up | 256 kB built-in flash memory for backup of programs |
Data storage equipment | 2 GB SD card optional |
Depth | 70 mm |
Discrete I/O number | 40 |
Discrete input current | 7 mA for input |
Discrete input logic | Sink or source (positive/negative) |
Discrete input number | 24 discrete input conforming to IEC 61131-2 Type 1 including 4 fast input |
Discrete input voltage | 24 V |
Discrete input voltage type | DC |
Discrete output current | 2 A |
Discrete output number | 16 relay |
Discrete output type | Relay normally open |
Discrete output voltage | 5...250 V AC 5...125 V DC |
Electrical connection | Mini B USB 2.0 connector for a programming terminal Connector, 4 terminal(s) for analogue inputs Terminal block, 3 terminal(s) for connecting the 24 V DC power supply Removable screw terminal block for outputs Removable screw terminal block for inputs |
Electrical durability | Inductive (L/R = 7 ms) DC-13, 24 V / 7.2 W : 300000 cycles Inductive (L/R = 7 ms) DC-13, 24 V / 24 W : 100000 cycles Resistive DC-12, 24 V / 16 W : 300000 cycles Resistive DC-12, 24 V / 48 W : 100000 cycles Inductive AC-14, (cos phi = 0.7) 240 V / 72 VA : |
Electromagnetic emission | Radiated emissions conforming to EN/IEC 55011 class A 10 m, 230 MHz...1 GHz : 47 dB?V/m QP Radiated emissions conforming to EN/IEC 55011 class A 10 m, 30...230 MHz : 40 dB?V/m QP Conducted emissions conforming to EN/IEC 55011 power lines, 1.5...30 MHz : 6 |
Exct time for event task | 60 µs response time |
Execution time for 1 KInstruction | 0.3 ms for event and periodic task |
Execution time per instruction | 0.2 µs Boolean |
Height | 70 mm |
Immunity to microbreaks | 10 ms |
Input impedance | 100 kOhm for analog input 3.4 kOhm for discrete input |
Inrush current | <= 40 A |
Insulation | Non-insulated between analogue inputs Non-insulated between analogue input and internal logic 500 V AC between output groups 500 V AC between output and internal logic Non-insulated between inputs 500 V AC between fast input and internal logic 500 V AC be |
Integrated connection type | Ethernet with connector RJ45 Non isolated serial link "serial 1" with connector RJ45 and interface RS232/RS485 USB port with connector mini B USB 2.0 |
IP degree of protection | IP20 with protective cover in place |
Local signalling | Ethernet network link yellow for Link (Link Status) Ethernet network activity green for ACT 1 LED green for SL 1 LED per channel green for I/O state 1 LED red for BAT 1 LED green for SD card access (SD) 1 LED red for module error (ERR) 1 LED green for RUN |
LSB value | 10 mV |
Marking | CE |
Mechanical durability | >= 20000000 cycles for relay output |
Memory capacity | 256 kB for program with 10000 instructions |
Minimum load | 10 mA at 5 V DC for relay output |
Mounting support | Plate or panel with fixing kit Top hat type TH35-7.5 rail conforming to IEC 60715 Top hat type TH35-15 rail conforming to IEC 60715 |
Network frequency | 50/60 Hz |
Number of I/O expansion module | <= 7 with <= 48 discrete output(s) for relay output |
Operating altitude | 0...2000 m |
Output voltage limits | 277 V AC 125 V DC |
Permitted overload on inputs | +/- 15 V DC for analog input permanent +/- 30 V DC for analog input with 5 min maximum |
Pollution degree | <= 2 |
Port Ethernet | 10BASE-T/100BASE-TX 1 port with 100 m copper cable |
Power consumption in VA | <= 41 VA at 100...240 V without I/O expansion module <= 70 VA at 100...240 V with max number of I/O expansion module |
Product certifications | CSA CULus IACS E10 RCM |
Product end of life instructions | Available Download End of life manual |
Product environmental profile | Available Download Product environmental |
Product or component type | Logic controller |
Product weight | 0.456 kg |
Range of product | Modicon M221 |
REACh | Reference contains SVHC above the threshold - Go to CaP for more details |
Regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
Relative humidity | 10...95 % without condensation in storage 10...95 % without condensation in operation |
Reset time | 1 s |
Resistance to conducted disturbances, induced by radio frequency fields | 10 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) conforming to Marine specification (LR, ABS, DNV, GL) 3 Vrms (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL) 10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000 |
Resistance to electromagnetic fields | 1 V/m ( 2 GHz...3 GHz) conforming to EN/IEC 61000-4-3 3 V/m ( 1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3 10 V/m ( 80 MHz...1 GHz) conforming to EN/IEC 61000-4-3 |
Resistance to electrostatic discharge | 4 kV on contact conforming to EN/IEC 61000-4-2 8 kV in air conforming to EN/IEC 61000-4-2 |
Resistance to fast transients | 1 kV for serial link conforming to EN/IEC 61000-4-4 1 kV for Ethernet line conforming to EN/IEC 61000-4-4 1 kV for I/O conforming to EN/IEC 61000-4-4 2 kV for relay output conforming to EN/IEC 61000-4-4 2 kV for power lines conforming to EN/IEC 61000-4-4 |
Resistance to magnetic fields | 30 A/m at 50...60 Hz conforming to EN/IEC 61000-4-8 |
Response time | 10 ms turn-off operation for output 10 ms turn-on operation for output 5 µs turn-off operation for fast input 5 µs turn-on operation for fast input 100 µs turn-off operation for input; I8...I15 terminal 100 µs turn-on operation for input; I8...I15 termina |
RoHS (date code: YYWW) | Compliant - since 1415 - Schneider Electric declaration of conformity |
Sensor power supply | 24 V DC at 250 mA supplied by the controller |
Shock resistance | 10 gn (test wave duration:11 ms) |
Standards | EN/IEC 61131-2 EN/IEC 61010-2-201 |
Storage altitude | 0...3000 m |
Supply | Serial serial link supply at 5 V 200 mA |
Supply voltage limits | 85...264 V |
Surge withstand | 1 kV for relay output in differential mode conforming to EN/IEC 61000-4-5 1 kV for power lines (AC) in differential mode conforming to EN/IEC 61000-4-5 0.5 kV for power lines (DC) in differential mode conforming to EN/IEC 61000-4-5 1 kV for shielded cable |
Sustainable offer status | Green Premium product |
Switching frequency | 20 switching operations/minute with maximum load |
Voltage state 0 guaranteed | <= 5 V for input |
Voltage state1 guaranteed | >= 15 V for input |
Width | 160 mm |
Transmission rate | 480 Mbit/s - communication protocol: USB 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m - communication protocol: RS232 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m - communication protocol: RS485 |
Vibration resistance | 3 gn (vibration frequency: 8.4...150 Hz) on panel mounting 3.5 mm (vibration frequency: 5...8.4 Hz) on panel mounting 3 gn (vibration frequency: 8.4...150 Hz) on symmetrical rail 3.5 mm (vibration frequency: 5...8.4 Hz) on symmetrical rail |