Ambient air temperature for operation | -10...55 °C for horizontal installation -10...35 °C for vertical installation |
Ambient air temperature for storage | -25...70 °C |
Cable length | <= 30 m unshielded cable for regular input |
Current consumption | 65 mA at 5 V DC via bus connector at state on 0 mA at 24 V DC via bus connector at state off 0 mA at 24 V DC via bus connector at state on 5 mA at 5 V DC via bus connector at state off |
Current per output common | 7 A |
Current state 0 guaranteed | <= 1 mA for input |
Current state 1 guaranteed | >= 2.5 mA for input |
Depth | 84.6 mm |
Discrete I/O number | 24 |
Discrete input current | 7 mA for input |
Discrete input logic | Sink or source (positive/negative) |
Discrete input number | 16 input conforming to IEC 61131-2 Type 1 |
Discrete input voltage | 24 V |
Discrete input voltage type | DC |
Discrete output current | 2000 mA for relay output |
Discrete output logic | Positive or negative |
Discrete output number | 8 |
Discrete output type | Relay normally open |
Discrete output voltage | 240 V AC for relay output 24 V DC for relay output |
Electrical connection | Removable spring terminal block pitch 3.81 mm with 11 terminal(s) of 1.5 mm² connection capacity for outputs Removable spring terminal block pitch 3.81 mm with 17 terminal(s) of 1.5 mm² connection capacity for inputs |
Electromagnetic emission | Radiated emissions, test level: 47 dB?V/m QP with class A, condition of test: 10 m (radio frequency: 230 MHz...1 GHz) conforming to EN/IEC 55011 Radiated emissions, test level: 40 dB?V/m QP with class A, condition of test: 10 m (radio frequency: 30...230 |
Height | 90 mm |
Input impedance | 3.4 kOhm |
IP degree of protection | IP20 with protective cover in place |
Local signalling | 1 LED per channel green for I/O state |
Marking | CE |
Mechanical durability | 20000000 cycles |
Minimum load | 10 mA at 5 V DC for relay output |
Mounting support | Plate or panel with fixing kit Top hat type TH35-7.5 rail conforming to IEC 60715 Top hat type TH35-15 rail conforming to IEC 60715 |
Insulation | Non-insulated between outputs 500 V AC between output and internal logic 750 V AC between open contact 1500 V AC between input groups and output groups Non-insulated between inputs 500 V AC between input and internal logic |
Operating altitude | 0...2000 m |
Pollution degree | 2 |
Product certifications | C-Tick CULus |
Product end of life instructions | Available Download End of life manual |
Product environmental profile | Available Download Product environmental |
Product or component type | Discrete I/O module |
Range compatibility | Modicon M221 Modicon M241 Modicon M251 |
Range of product | Modicon TM3 |
REACh | Reference not containing SVHC above the threshold |
Relative humidity | 10...95 % without condensation in storage 10...95 % without condensation in operation |
Resistance to conducted disturbances, induced by radio frequency fields | 3 Vrms at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) 10 Vrms at 0.15...80 MHz conforming to EN/IEC 61000-4-6 |
Resistance to electromagnetic fields | 1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 |
Resistance to electrostatic discharge | 4 kV (on contact) conforming to EN/IEC 61000-4-2 8 kV (in air) conforming to EN/IEC 61000-4-2 |
Resistance to fast transients | 2 kV for relay output conforming to EN/IEC 61000-4-4 1 kV for I/O conforming to EN/IEC 61000-4-4 |
Resistance to magnetic fields | 30 A/m at 50...60 Hz conforming to EN/IEC 61000-4-8 |
Response time | 4 ms for turn-off 4 ms for turn-on |
RoHS (date code: YYWW) | Compliant - since 1348 - Schneider Electric declaration of conformity |
Shock resistance | 15 gn (test wave duration:11 ms) |
Standards | EN/IEC 61131-2 EN/IEC 61010-2-201 |
Storage altitude | 0...3000 m |
Surge withstand | 1 kV for input in common mode conforming to EN/IEC 61000-4-5 2 kV for output in common mode conforming to EN/IEC 61000-4-5 |
Sustainable offer status | Green Premium product |
Vibration resistance | 3 gn (vibration frequency: 8.4...150 Hz) on panel 3.5 mm (vibration frequency: 5...8.4 Hz) on panel 3 gn (vibration frequency: 8.4...150 Hz) on DIN rail 3.5 mm (vibration frequency: 5...8.4 Hz) on DIN rail |
Voltage state 0 guaranteed | 0...5 V for input |
Voltage state1 guaranteed | 15...28.8 V for input |
Width | 42.9 mm |