Navigér
Sœg

TM3-Busmodul. Sender


Varenr:TM3XTRA1
El nr:7586047742
EAN13 nr:3606480611230
Pakning:1stk

Ambient air temperature for operation-10...50 °C for vertical installation -10...55 °C for horizontal installation
Ambient air temperature for storage-40...70 °C
Cable length0.5...5 m extension cable with 2 RJ45 conductor between receiver and transmitter
Current consumption30 mA at 5 V DC via bus connector at state off 100 mA at 5 V DC via bus connector at state on
Depth73.3 mm
Electrical connectionScrew connector terminal for connecting the functional ground RJ45 connector for connecting the bus receiver
Electromagnetic emissionRadiated emissions - EN/IEC 55011 class A 10 m, 230 MHz...1 GHz : 47 dB?V/m QP Radiated emissions - EN/IEC 55011 class A 10 m, 30...230 MHz : 40 dB?V/m QP
Height90 mm
IP degree of protectionIP20 with protective cover in place
Local signalling1 LED green for link status 1 LED green for power supply
MarkingCE
Mounting supportPlate or panel with fixing kit Top hat type TH35-7.5 rail conforming to IEC 60715 Top hat type TH35-15 rail conforming to IEC 60715
Operating altitude0...2000 m
Pollution degree2
Power dissipation in W<= 0.6 W
Product certificationsCSA HazLoc C-Tick GOST Merchant Navy
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product or component typeRemote transmitter module
Product weight0.065 kg
Range compatibilityModicon M221 Modicon M241 Modicon M251
Range of productModicon TM3
REAChReference not containing SVHC above the threshold
Relative humidity5...95 % without condensation
Resistance to conducted disturbances, induced by radio frequency fields3 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) - Marine specification (LR, ABS, DNV, GL) 10 Vrms (0.15...80 MHz) - EN/IEC 61000-4-6
Resistance to electromagnetic fields1 V/m (2...2.7 GHz) - EN/IEC 61000-4-3 3 V/m (1.4 GHz...2 GHz) - EN/IEC 61000-4-3 10 V/m (80 MHz...1 GHz) - EN/IEC 61000-4-3
Resistance to electrostatic discharge6 kV on contact - EN/IEC 61000-4-2 8 kV in air - EN/IEC 61000-4-2
RoHS (date code: YYWW)Compliant - since 1408 -  Schneider Electric declaration of conformity
Shock resistance15 gn (test wave duration:11 ms)
StandardsUL 508 IEC 61131-2 CSA C22.2 No 142 UL 1604 (Class I Division 2 Groups A/B/C) CSA C22.2 No 213 (Class I Division 2 Groups A/B/C/D)
Storage altitude0...3000 m
Sustainable offer statusGreen Premium product
Vibration resistance3 gn (vibration frequency: 8.4...150 Hz) on panel 3.5 mm (vibration frequency: 5...8.4 Hz) on panel 3 gn (vibration frequency: 8.4...150 Hz) on DIN rail 3.5 mm (vibration frequency: 5...8.4 Hz) on DIN rail
Width23.65 mm

Yderliger oplysninger: Se venligst SE katalog