[Us] rated supply voltage | 24 V DC by external supply (- 15...20 %) |
Ambient air temperature for operation | Horizontal installation : -10...55 °C Vertical installation : -10...35 °C |
Ambient air temperature for storage | -25...70 °C |
Current consumption | 1200 mA at 24 V DC external power supply at state on 10 mA at 24 V DC via bus connector at state off 0 mA at 24 V DC via bus connector at state on 35 mA at 5 V DC via bus connector at state off 5 mA at 5 V DC via bus connector at state on |
Depth | 85 mm |
Electromagnetic emission | Radiated emissions - EN/IEC 55011 class A 10 m, 230 MHz...1 GHz : 47 dB?V/m QP Radiated emissions - EN/IEC 55011 class A 10 m, 30...230 MHz : 40 dB?V/m QP |
Height | 90 mm |
Input current limits | 5 mA per input |
Input voltage limits | 19.2...28.8 V per input |
Insulation | Non-insulated between RJ45 connectors Between the RJ45 connectors and internal logic : 500 V AC |
IP degree of protection | IP20 with protective cover in place |
Local signalling | 2 LEDs green per channel for output status 3 LEDs green per channel for input status |
Electrical connection | 4 RJ45 connectors for connecting the motor starters Removable screw terminal block with pitch 5.08 mm, clamping capacity 2.5 mm², 3 terminals for connecting the 24 V DC power supply |
Marking | CE |
Maximum load current | 300 mA per channel in normal mode 800 mA per channel in starting mode during 100 ms |
Mounting support | Plate or panel with fixing kit Rail top hat type TH35-7.5 conforming to IEC 60715 Rail top hat type TH35-15 conforming to IEC 60715 |
Number of input channels | 12 |
Number of output channels | 8 |
Operating altitude | 0...2000 m |
Output protection type | Against overload by current limiter |
Output voltage | 24 V DC (transistor output) |
Pollution degree | 2 |
Product certifications | C-Tick CULus |
Product end of life instructions | Available Download End of life manual |
Product environmental profile | Available Download Product environmental |
Product or component type | Parallel interface module |
Product specific application | TeSys Quickfit TeSys U TeSys D |
Product weight | 0.115 kg |
Range compatibility | Modicon M221 Modicon M241 Modicon M251 |
Range of product | Modicon TM3 |
REACh | Reference not containing SVHC above the threshold |
Relative humidity | 10...95 % without condensation in storage 10...95 % without condensation in operation |
Reset | Automatic reset |
Resistance to conducted disturbances, induced by radio frequency fields | 3 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) - Marine specification (LR, ABS, DNV, GL) 10 Vrms (0.15...80 MHz) - EN/IEC 61000-4-6 |
Resistance to electromagnetic fields | 1 V/m (2 GHz...3 GHz) - EN/IEC 61000-4-3 3 V/m (1.4 GHz...2 GHz) - EN/IEC 61000-4-3 10 V/m (80 MHz...1 GHz) - EN/IEC 61000-4-3 |
Resistance to electrostatic discharge | 4 kV on contact - EN/IEC 61000-4-2 8 kV in air - EN/IEC 61000-4-2 |
Resistance to fast transients | 1 kV for output - EN/IEC 61000-4-4 1 kV for input - EN/IEC 61000-4-4 |
Resistance to magnetic fields | 30 A/m (50...60 Hz) - EN/IEC 61000-4-8 |
Response time | < 10 ms turn-off for input < 10 ms turn-on for input |
RoHS (date code: YYWW) | Compliant - since 1348 - Schneider Electric declaration of conformity |
Shock resistance | 15 gn during 11 ms |
Standards | EN/IEC 61131-2 EN/IEC 61010-2-201 |
Storage altitude | 0...3000 m |
Surge withstand | 1 kV for output in common mode - EN/IEC 61000-4-5 1 kV for input in common mode - EN/IEC 61000-4-5 |
Sustainable offer status | Green Premium product |
Vibration resistance | 3 gn (f = 8.4...150 Hz) on panel 3.5 mm (f = 5...8.4 Hz) on panel 3 gn (f = 8.4...150 Hz) on DIN rail 3.5 mm (f = 5...8.4 Hz) on DIN rail |
Width | 30 mm |