[Ithe] conventional enclosed thermal current | <= 2.5 A |
[Ue] rated operational voltage | 19...250 V AC relæ udgang 17...127 V DC relæ udgang |
[Us] rated supply voltage | 24 V DC |
Activation threshold | < 20 V |
Ambient air temperature for operation | 0...60 °C with fan module 0...40 °C without fan |
Ambient air temperature for storage | -25...70 °C |
Digital indgangslogik | Positiv |
Digital indgangsnummer | 12 emergency stop or limit switch discrete inputs conforming to IEC 1131 Type 1 1 reset PB monitoring input conforming to IEC 1131 Type 1 1 reset PB input conforming to IEC 1131 Type 1 1 feedback loop input conforming to IEC 1131 Type 1 1 double or single |
Effekttab i W | < 5 W |
Elektrisk tilslutning | 1 forbindelse SUB-D 44 pins for connecting the safety system 1 forbindelse aftagelig skrue terminal 6 pins |
Forsyningsspændingsgrænser | 19.2...30 V |
Indkoblingsstrøm | <= 0.5 A |
IP kapslingsklasse | 18-22 conforming to IEC 60529 |
Iso between input and earth | 500 Vrms 50/60 Hz for 60 s |
Isolation between output and earth | 1500 Vrms 50/60 Hz for 60 s 300 V conforming to DIN VDE 0110 part 2 |
Isolationsspænding | 4000 V III 2 |
Ledertværsnit | 1.5 mm² med kabel ende safety output circuit 0.2...2.5 mm² without cable end safety output circuit |
Lokal indikering | 28 LEDs diagnostic of safety system |
Minimum udgangsstrøm | >= 30 mA |
Modulformat | Standard |
Mærkeeffekt i VA | 60 VA 24 V AC-15 inductiv 550 VA 220 V AC-15 inductiv 280 VA 110 V AC-15 inductiv 120 VA 48 V AC-15 inductiv |
Mærkeeffekt i W | 60 W 24 V DC-13 inductiv 100 ms |
Productcertificeringer | BG CSA UL |
Produkttype | Preventa safety module |
Range of product | Modicon Premium Automation platform |
Responstid på udgang | < 12 ms |
RoHS EUR conformity date(YYWW) | 0905 |
RoHS EUR status | Compliant |
Safety acquisition | Monitor external power supply of the module Read enable inputs Read feedback loop Read the safety outputs control Read status of the 24 inputs |
Short circuit protection | 4 A gG ekstern conforming to IEC 947-5-1 for F2 on safety relay outputs 1 A gG ekstern conforming to IEC 947-5-1 for F1 on power supply |
Sikkerhedsudgange | 4 NO safety relay AGCDO gold plated volt free output |
Standarder | CSA C22.2 specific requirements (PLC) IEC 61508 SIL 3 machine safety parts of control systems ISO 13849-1 category 4 machine safety parts of control systems UL 508 specific requirements (PLC) ISO 13850 emergency stop equipment EN/ISO 12100 machine electri |
Strømforbrug | <= 200 mA 24 V DC < 150 mA 5 V DC |
Vægt | 0.49 kg |