Navigér
Sœg

Endestop reset stemp/rulle NC+NC med moment


Varenr:XCNR2902P20
El nr:7524018607
EAN13 nr:3389119034401
Pakning:1stk

[Ui] rated insulation voltage300 V conforming to CSA C22.2 No 14 500 V degree of pollution 3 conforming to EN/IEC 60947-1 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1 6 kV conforming to IEC 60664
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
Body materialPlastic
Body typeFixed
Cable entry1 entry tapped for M20 x 1.5 cable gland, cable outer diameter: 7...13 mm
Class of protection against electric shockClass II conforming to NF C 20030 Class II conforming to IEC 61140
Contact code designationR300, DC-13 (Ue = 250 V, Ie = 0.1 A) conforming to EN/IEC 60947-5-1 appendix A A300, AC-15 (Ue = 240 V, Ie = 3 A) , Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A
Contacts insulation formZb
Contacts operationSnap action
Contacts type and composition2 NC
Device short nameXCNR
Electrical connectionScrew-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm²
Fixing modeBy the body
Head materialPlastic
Head typePlunger head
IK degree of protectionIK04 conforming to EN 50102
IP degree of protectionIP65 conforming to IEC 60529
MaterialPlastic
Maximum actuation speed0.3 m/s
Mechanical durability100000 cycles
Minimum force for tripping12 N
Movement of operating headLinear
Number of poles2
Positive openingWith
Positive opening minimum force20 N
Product certificationsCCC CSA UL
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product or component typeLimit switch
Protective treatmentTC
Range of productOsiSense XC
REAChReference not containing SVHC above the threshold
ResetWith
RoHS (date code: YYWW)Compliant - since 1038 -  Schneider Electric declaration of conformity
Sensor designCompact
Series nameStandard format
Shock resistance50 gn (duration = 11 ms) conforming to IEC 60068-2-27
Short circuit protection10 A cartridge fuse type gG
StandardsEN 60204-1 EN 60947-5-1 IEC 60204-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Switch actuationBy 30° cam
Type of approachLateral approach 2 directions
Type of operatorSpring return roller plunger plastic
Vibration resistance25 gn 10...500 Hz IEC 60068-2-6

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info