[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 6 kV conforming to IEC 60664 |
Ambient air temperature for operation | -25...70 °C |
Ambient air temperature for storage | -40...70 °C |
Body material | Plastic |
Body type | Fixed |
Cable entry | 1 entry tapped for Pg 13.5 cable gland, cable outer diameter: 9...12 mm |
Class of protection against electric shock | Class II conforming to NF C 20-030 Class II conforming to IEC 61140 |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 500 V degree of pollution 3 conforming to IEC 60947-1 500 V degree of pollution 3 conforming to EN 60947-1 300 V conforming to UL 508 |
Contact code designation | Q300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1 appendix A A300, AC-15 (Ue = 240 V, Ie = 3 A) , Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A |
Contacts insulation form | Zb |
Contacts operation | Snap action |
Contacts type and composition | 1 NC + 1 NO |
Depth | 30 mm |
Device short name | XCPR |
Electrical connection | Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm² |
Electrical durability | 5000000 cycles DC-13 48 V 7 W <= 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles DC-13 24 V 10 W <= 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles DC-13 120 V 4 W <= 60 cyc/mn 0.5 IEC 60947-5-1 appendix C |
Fixing mode | By the body |
Head material | Zamak |
Head type | Plunger head |
Height | 65 mm |
IK degree of protection | IK04 conforming to EN 50102 |
IP degree of protection | IP67 conforming to IEC 60529 IP66 conforming to IEC 60529 |
Material | Plastic |
Maximum actuation speed | 1 m/s |
Minimum force for tripping | 6 N |
Movement of operating head | Linear |
Number of poles | 2 |
Positive opening | With |
Positive opening minimum force | 18 N |
Product certifications | CSA UL |
Product end of life instructions | Available Download End of life manual |
Product environmental profile | Available Download Product environmental |
Product or component type | Limit switch |
Product weight | 0.12 kg |
Protective treatment | TC |
Range of product | OsiSense XC |
REACh | Reference not containing SVHC above the threshold |
Reset | With |
Resistance across terminals | <= 25 MOhm conforming to IEC 60255-7 category 3 |
RoHS (date code: YYWW) | Compliant - since 1037 - Schneider Electric declaration of conformity |
Sensor design | Compact |
Series name | Standard format |
Shock resistance | 50 gn (duration = 11 ms) conforming to IEC 60068-2-27 |
Short circuit protection | 10 A by gG cartridge fuse |
Standards | EN 60204-1 EN 60947-5-1 IEC 60204-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
Sustainable offer status | Green Premium product |
Switch actuation | By 30° cam |
Terminals description ISO n°1 | (13-14)NO (21-22)NC |
Type of approach | Vertical approach 1 direction |
Type of operator | Spring return roller lever plunger thermoplastic |
Vibration resistance | 25 gn (f = 10...500 Hz) conforming to IEC 60068-2-6 |
Width | 31 mm |