[Ui] rated insulation voltage300 V conforming to CSA C22.2 No 14 500 V degree of pollution 3 conforming to IEC 60947-1 500 V degree of pollution 3 conforming to EN 60947-1 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1 6 kV conforming to IEC 60664
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
Body materialPlastic
Body typeFixed
Cable entry1 entry tapped for M20 x 1.5 cable gland, cable outer diameter: 7...13 mm
Class of protection against electric shockClass II conforming to NF C 20-030 Class II conforming to IEC 61140
Contacts insulation formZb
Contacts operationSnap action
Contacts type and composition1 NC + 1 NO
Contact code designationQ300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1 appendix A A300, AC-15 (Ue = 240 V, Ie = 3 A) , Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A
Depth30 mm
Device short nameXCPR
Electrical connectionScrew-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm²
Electrical durability5000000 cycles DC-13 48 V 7 W <= 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles DC-13 24 V 10 W <= 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles DC-13 120 V 4 W <= 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Fixing modeBy the body
Head materialZamak
Head typePlunger head
Height65 mm
IK degree of protectionIK04 conforming to EN 50102
IP degree of protectionIP67 conforming to IEC 60529 IP66 conforming to IEC 60529
MaterialPlastic
Maximum actuation speed1 m/s
Minimum force for tripping6 N
Movement of operating headLinear
Number of poles2
Positive openingWith
Positive opening minimum force18 N
Product certificationsCSA UL
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product or component typeLimit switch
Product weight0.12 kg
Protective treatmentTC
Range of productOsiSense XC
REAChReference not containing SVHC above the threshold
ResetWith
Resistance across terminals<= 25 MOhm conforming to IEC 60255-7 category 3
RoHS (date code: YYWW)Compliant - since 1037 -  Schneider Electric declaration of conformity
Sensor designCompact
Series nameStandard format
Shock resistance50 gn (duration = 11 ms) conforming to IEC 60068-2-27
Short circuit protection10 A by gG cartridge fuse
StandardsEN 60204-1 EN 60947-5-1 IEC 60204-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Switch actuationBy 30° cam
Terminals description ISO n°1(13-14)NO (21-22)NC
Type of approachVertical approach 1 direction
Type of operatorSpring return roller lever plunger thermoplastic
Vibration resistance25 gn (f = 10...500 Hz) conforming to IEC 60068-2-6