[Ithe] conventional enclosed thermal current | 10 A |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 500 V conforming to EN/IEC 60947-1 300 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-5-1 |
Actuator force for extraction | >= 20 N |
Ambient air temperature for operation | -25...70 °C |
Ambient air temperature for storage | -40...70 °C |
Body material | Zamak |
Cable entry number | 1 tapped entry (M20 x 1.5) for cable gland (included), cable outer diameter: 7...13 mm |
CAD overall depth | 44 mm |
CAD overall height | 114 mm |
CAD overall width | 40 mm |
Clamping connection capacity | 1 x 0.5...2 x 1.5 mm² with or without cable end |
Class of protection against electric shock | Class I conforming to EN/IEC 60536 |
Contact code designation | Q300, DC-13 (250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1 Q300, DC-13 (125 V, Ie = 0.55 A) conforming to EN/IEC 60947-5-1 A300, AC-15 (240 V, Ie = 3 A) conforming to EN/IEC 60947-5-1 A300, AC-15 (120 V, Ie = 6 A) conforming to EN/IEC 60947-5-1 |
Contacts operation | Slow-break, break before make |
Contacts type and composition | 2 NC + 1 NO |
Device short name | XCSA |
Dust zone | Zone 21 - 22 |
Electrical connection | Terminal |
Head material | Zamak |
Head type | Key operated turret head |
IP degree of protection | IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1 |
Local signalling | Without |
Locking options description | Without locking of actuator |
Marking | II2 D-Ex tb IIIC T85°C Db IP67 |
Material | Metal |
Maximum actuation speed | 0.5 m/s |
Mechanical durability | >= 1000000 cycles |
Minimum actuation speed | 0.01 m/s |
Number of poles | 3 |
Operating rate | 10 cyc/mn for maximum durability |
Positive opening | With NC contact |
Product certifications | CSA INERIS 04ATEX0014X UL |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product or component type | Safety switch |
Product weight | 0.44 kg |
Protective treatment | TC |
Range of product | Preventa ATEX D |
REACh | Reference not containing SVHC above the threshold |
RoHS | Compliant - since 0941 - Schneider Electric declaration of conformity |
Safety level | Can reach SIL 3 conforming to IEC 61508 with the appropriate monitoring system and correctly wired Can reach PL = e conforming to EN/ISO 13849-1 with the appropriate monitoring system and correctly wired Can reach category 4 conforming to EN/ISO 13849-1 w |
Safety reliability data | B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear |
Shock resistance | 10 gn for 11 ms conforming to IEC 60068-2-27 |
Short circuit protection | 10 A cartridge fuse, gG (gl) |
Standards | Directive ATEX 94/9/EC EN/IEC 60079-0 EN/IEC 60079-31 |
Sustainable offer status | Green Premium product |
Vibration resistance | 5 gn (f = 10...500 Hz) conforming to IEC 60068-2-6 |