[Ie] rated operational current | <= 100 A |
[Sa] assured operating distance | 5 mm |
[Sar] assured tripping distance | 15 mm |
[Ue] rated operational voltage | 24 V DC |
[Ui] rated insulation voltage | 100 V DC |
[Uimp] rated impulse withstand voltage | 2.5 kV conforming to EN/IEC 60947-5-1 |
Ambient air temperature for operation | -25...85 °C |
Ambient air temperature for storage | -40...85 °C |
Approach directions | 3 directions |
Breaking capacity | <= 10 VA |
Cable composition | 4 x 0.25 mm² |
Cable length | 2 m |
Cable material | PVC |
Class of protection against electric shock | Class II conforming to IEC 60536 |
Contacts material | Rhodium |
Contacts operation | Staggered |
Contacts type and composition | 1 NC + 1 NO |
Design | Rectangular, compact |
Device short name | XCSDMC |
Dust zone | Zone 0 - 1 - 2/20 - 21 - 22 According to protection mode mD, tD and ia |
Electrical connection | Pre-cabled |
Electrical durability | 1200000 cycles |
Enclosure material | Thermoplastic PBT |
Insulation resistance | 1000 MOhm |
IP degree of protection | IP67 conforming to IEC 60529 IP66 conforming to IEC 60529 |
Marking | II2 G/D-Ex ia A0/20 IP67 T135°C II2 G/D-Ex Ex mb II T4 II1 G/D-Ex ia IIB T4 II1 G/D-Ex iaD 20 T135°C |
Material | Plastic |
Maximum switching voltage | 100 V DC |
Number of poles | 2 |
Product certifications | BG CSA UL INERIS 04ATEX0036 |
Product or component type | Coded magnetic switch |
Product weight | 0.101 kg |
Protective treatment | TH |
Range of product | Preventa ATEX D |
Resistance across terminals | 10 Ohm |
RoHS | Compliant - since 0915 - Schneider Electric declaration of conformity |
Safety level | Can reach SIL 3 conforming to IEC 61508 with the appropriate monitoring system and correctly wired Can reach PL = e conforming to EN/ISO 13849-1 with the appropriate monitoring system and correctly wired Can reach category 4 conforming to EN/ISO 13849-1 w |
Safety reliability data | B10d = 50000000 value given for a life time of 20 years limited by mechanical or contact wear |
Sensitivity to magnetic fields | >= 0.3 mT |
Shock resistance | 30 gn for 11 ms conforming to IEC 60068-2-27 |
Short circuit protection | 500 mA external cartridge fuse, gG (gl) |
Size | 51 x 16 x 7 mm |
Standards | Directive ATEX 94/9/EC EN 1088 EN/ISO 13849-1 EN 60079-0 EN 60079-18 EN 60079-31 |
Sustainable offer status | Not Green Premium product |
Switching capacity in mA | 0.1...100 mA |
Switching frequency | 150 Hz |
Vibration resistance | 10 gn (f = 10...150 Hz) conforming to IEC 60068-2-6 |