 |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 400 V (degree of pollution: 3) conforming to IEC 60947-5-1 300 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-1 4 kV conforming to IEC 60664 |
Ambient air temperature for operation | -25...70 °C |
Ambient air temperature for storage | -40...70 °C |
Body material | Zamak |
Cable composition | 9 x 0.34 mm² |
Cable length | 1 m |
Class of protection against electric shock | Class I conforming to NF C 20-030 Class I conforming to IEC 6140 |
Component name | XCSM |
Contact code designation | R300, DC-13 (Ue = 250 V, Ie = 0.1 A) conforming to EN/IEC 60947-5-1 appendix A R300, DC-13 (Ue = 250 V, Ie = 0.1 A) conforming to EN 60947-5-1 B300, AC-15 (Ue = 240 V, Ie = 1.5 A) conforming to EN/IEC 60947-5-1 appendix A B300, AC-15 (Ue = 240 V, Ie = 1.5 |
Contacts operation | Snap action |
Contacts type and composition | 1 NC + 1 NC + 1 NO + 1 NO |
Depth | 34 mm |
Design | Miniature |
Electrical connection | Pre-cabled |
Fixing mode | By the body |
Head material | Zamak |
Head type | Rotary head |
Height | 94 mm |
IK degree of protection | IK06 conforming to EN 50102 |
IP degree of protection | IP68 conforming to IEC 60529 IP67 conforming to IEC 60529 IP66 conforming to IEC 60529 |
Material | Metal |
Maximum actuation speed | 1.5 m/s |
Mechanical durability | 10000000 cycles |
Minimum actuation speed | 0.01 m/min |
Minimum torque for tripping | 0.5 N.m |
Number of poles | 4 |
Positive opening | With NC contact |
Positive opening minimum torque | 0.1 N.m |
Product certifications | CSA UL |
Product end of life instructions | Available Download End of life manual |
Product environmental profile | Available Download Product environmental |
Product or component type | Safety limit switch |
Product weight | 0.21 kg |
Protection technology | Plastic protective cover, secured by 5-lobe socket head safety screw |
Protective treatment | TC |
Range of product | Preventa Safety detection |
REACh | Reference not containing SVHC above the threshold |
Repeat accuracy | 0.05 mm on the tripping points |
Resistance across terminals | <= 25 MOhm conforming to IEC 60255-7 category 3 |
RoHS (date code: YYWW) | Compliant - since 1002 - Schneider Electric declaration of conformity |
Safety level | Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to IEC 61508 Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1 Can reach category 4 with the appropriate monitorin |
Safety reliability data | B10d = 50000000 (value given for a life time of 20 years limited by mechanical or contact wear) |
Shock resistance | 25 gn for 18 ms conforming to IEC 60068-2-27 |
Short circuit protection | 6 A cartridge fuse type gG (gl) |
Standards | EN 1088 EN/IEC 60204-1 EN/IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
Sustainable offer status | Green Premium product |
Switch actuation | By 30° cam |
Type of approach | Lateral approach |
Type of operator | Steel roller lever |
Vibration resistance | 5 gn (f = 10...500 Hz) conforming to IEC 60068-2-6 |
Width | 30 mm |