[Ie] rated operational current | 1.5 A at 120 V utilisation category AC-15, C300 conforming to EN/IEC 60947-5-1 0.75 A at 240 V utilisation category AC-15, C300 conforming to EN/IEC 60947-5-1 0.27 A at 250 V utilisation category DC-13, Q300 conforming to EN/IEC 60947-5-1 0.55 A at 125 V |
[Ithe] conventional enclosed thermal current | 2.5 A |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 500 V conforming to EN/IEC 60947-1 300 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-5-1 |
Actuator force for extraction | >= 8 N |
Actutr forcible withdrawal rtc | 8 N |
Ambient air temperature for operation | -25...70 °C |
Ambient air temperature for storage | -25...80 °C |
Body material | PA (polyamide) |
Cable composition | 4 x 0.5 mm² |
Cable length | 5 m |
Class of protection against electric shock | Class II conforming to EN/IEC 60536 |
Component name | XCSMP |
Contacts operation | Slow-break, break before make |
Contacts type and composition | 1 NC + 1 NO |
Depth | 30 mm |
Design | Miniature |
Electrical connection | Pre-cabled |
Head material | PA (polyamide) |
Head type | Key operated fixed head |
Height | 87 mm |
Insulation | Double insulated |
IP degree of protection | IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1 |
Locking options description | Without locking of actuator |
Material | Plastic |
Maximum actuation speed | 1.5 m/s |
Mechanical durability | >= 1000000 cycles |
Minimum actuation speed | 0.05 m/s |
Number of poles | 2 |
Operating rate | 20 cyc/mn for maximum durability |
Positive opening | With NC contact |
Product certifications | CSA CUL UL |
Product or component type | Safety switch |
Product weight | 0.11 kg |
Protective treatment | TC |
Range of product | Preventa Safety detection |
RoHS (date code: YYWW) | Compliant - since 0642 - Schneider Electric declaration of conformity |
Safety level | Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508 Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1 Can reach category 4 with the appropriate monito |
Safety reliability data | B10d = 5000000 (value given for a life time of 20 years limited by mechanical or contact wear) |
Shock resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
Short circuit protection | 10 A cartridge fuse type gG (gl) |
Standards | EN 1088/ISO 14119 EN/IEC 60204-1 EN/IEC 60947-5-1 EN/ISO 12100 UL 508 CSA C22.2 No 14 |
Sustainable offer status | Not Green Premium product |
Vibration resistance | 6 gn (f = 10...55 Hz) conforming to IEC 60068-2-6 |
Width | 15 mm |