Navigér
Sœg

Lågekontakt plast med nøgle 2N/C+1N/O


Varenr:XCSPA992
El nr:7524018636
EAN13 nr:3389119028585
Pakning:1stk

[Ie] rated operational current0.27 A at 250 V utilisation category DC-13, Q300 conforming to EN/IEC 60947-5-1 0.55 A at 125 V utilisation category DC-13, Q300 conforming to EN/IEC 60947-5-1 3 A at 240 V utilisation category AC-15, A300 conforming to EN/IEC 60947-5-1 6 A at 120 V utili
[Ithe] conventional enclosed thermal current10 A
[Ui] rated insulation voltage400 V (degree of pollution: 3) conforming to IEC 60947-1 300 V conforming to CSA C22.2 No 14 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60947-5-4
Actutr forcible withdrawal rtc10 N
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
Body materialPA (polyamide)
Cable entry1 entry tapped M16 x 1.5
Cable outer diameter7...10 mm
Class of protection against electric shockClass II conforming to EN/IEC 60536
Component nameXCSPA
Contacts operationSlow-break, break before make
Contacts type and composition2 NC + 1 NO
Depth30 mm
DesignCompact
Electrical connectionTerminal, 1 x 0.34...2 x 0.75 mm²
Head materialPA (polyamide)
Head typeKey operated turret head
Height94 mm
InsulationDouble insulated
IP degree of protectionIP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Locking options descriptionWithout locking of actuator
MaterialPlastic
Maximum actuation speed0.5 m/s
Mechanical durability>= 1000000 cycles
Minimum actuation speed0.01 m/s
Number of poles3
Operating rate10 cyc/mn for maximum durability
Positive openingWith NC contact
Positive opening minimum force15 N
Product certificationsCSA UL
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product or component typeSafety switch
Product weight0.11 kg
Protective treatmentTC
Range of productPreventa Safety detection
REAChReference not containing SVHC above the threshold
RoHS (date code: YYWW)Compliant - since 1010 -  Schneider Electric declaration of conformity
Safety levelCan reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508 Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1 Can reach category 4 with the appropriate monito
Safety reliability dataB10d = 5000000 (value given for a life time of 20 years limited by mechanical or contact wear)
Shock resistance10 gn for 11 ms conforming to IEC 60068-2-27
Short circuit protection6 A cartridge fuse type gG (gl)
StandardsEN 1088/ISO 14119 EN/IEC 60204-1 EN/IEC 60947-5-1 EN/ISO 12100 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Vibration resistance5 gn (f = 10...500 Hz) conforming to IEC 60068-2-6
Width30 mm

Yderliger oplysninger: Se venligst SE katalog