Navigér
Sœg

Sikkerhedsendestop plastik XCSTE - 2NC - slow break - 1 entry tapped 1/2'' NPT -24V


Varenr: XCSTE7513
Produktet findes ikke i SAP!

[Ithe] conventional enclosed thermal current6 A
[Ui] rated insulation voltage300 V conforming to CSA C22.2 No 14 500 V conforming to EN/IEC 60947-1 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-5-1
[Ie] rated operational current1.5 A at 240 V utilisation category AC-15, B300 conforming to EN/IEC 60947-5-1 3 A at 120 V utilisation category AC-15, B300 conforming to EN/IEC 60947-5-1 0.27 A at 250 V utilisation category DC-13, Q300 conforming to EN/IEC 60947-5-1 0.55 A at 125 V uti
[Us] solenoid rated supply  voltage24 V (- 20...10 %)
Actutr forcible withdrawal rtc500 N
Ambient air temperature for operation-25...60 °C
Ambient air temperature for storage-40...70 °C
Body materialPA (polyamide)
Cable entry1 entry tapped 1/2" NPT
Class of protection against electric shockClass II conforming to EN/IEC 60536
Component nameXCSTE
Contacts operationSlow-break, simultaneous
Contacts type and composition2 NC
Depth33 mm
DesignRectangular
Electrical connectionTerminal, 1 x 0.5...2 x 1.5 mm² with or without cable end
Electromagnet interlockingLocking on energisation and unlocking on de-energisation of solenoid
Head materialPA (polyamide)
Head typeKey operated turret head
Height94 mm
InsulationDouble insulated
IP degree of protectionIP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Load factor1
Locking options descriptionWith interlocking, locking by solenoid
MaterialPlastic
Maximum actuation speed0.5 m/s
Mechanical durability1000000 cycles
Minimum actuation speed0.01 m/s
Number of poles2
Operating rate10 cyc/mn for maximum durability
Positive openingWith NC contact
Positive opening minimum force15 N
Power consumption in VA10 VA
Product certificationsCSA UL
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product or component typeSafety switch
Product weight0.36 kg
Protective treatmentTC
Range of productPreventa Safety detection
REAChReference not containing SVHC above the threshold
RoHS (date code: YYWW)Compliant - since 1150 -  Schneider Electric declaration of conformity
Safety levelCan reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508 Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1 Can reach category 4 with the appropriate monito
Safety reliability dataB10d = 5000000 (value given for a life time of 20 years limited by mechanical or contact wear)
Shock resistance10 gn for 11 ms conforming to IEC 60068-2-27
Short circuit protection10 A cartridge fuse type gG (gl)
Solenoid contacts type and composition1 NC (slow-break)
StandardsEN 1088/ISO 14119 EN/IEC 60204-1 EN/IEC 60947-5-1 EN/ISO 12100 UL 508 CSA C22.2 No 14
Supply frequency50/60 Hz
Supply voltage typeAC/DC
Sustainable offer statusGreen Premium product
Vibration resistance5 gn (f = 10...500 Hz) conforming to IEC 60068-2-6
Width110 mm