Navigér
Sœg

Endestop contact block - 1NC+1NO - slow-break, meterake before break


Varenr: XE2NP3161
Produktet findes ikke i SAP!

[Ui] rated insulation voltage300 V conforming to CSA C22.2 No 14 500 V degree of pollution 3 conforming to IEC 60947-1 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1 6 kV conforming to IEC 60664
Associated bodyZCT26
Contact code designationQ300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1 appendix A A300, AC-15 (Ue = 240 V, Ie = 3 A) , Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A
Contacts insulation formZb
Contacts materialSilver plated contacts
Contacts operationSlow-break, make before break
Contacts type and composition1 NO + 1 NC
Device short nameXE2N
Electrical connectionScrew-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Electrical durability5000000 cycles, DC-13 48 V, 9 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC-13 24 V, 13 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC
Minimum actuation speed6 m/min
Number of poles2
Positive openingWith
Product compatibilityXCKT
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Product or component typeLimit switch contact block
Range of productOsiSense XC
REAChReference not containing SVHC above the threshold
Resistance across terminals< 25 mOhm conforming to IEC 60255-7 category 3
RoHS (date code: YYWW)Will not be Compliant
Series nameStandard format
Short circuit protection10 A by gG cartridge fuse
Sustainable offer statusNot Green Premium product

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info