Navigér
Sœg

Pressostat 20-300BAR


Varenr:XMLA300D2S11
El nr:7524673806
EAN13 nr:3389110712261
Pakning:1stk

[In] rated current0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1 3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage300 V conforming to CSA C22.2 No 14 500 V conforming to EN/IEC 60947-1 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-1
Adjustable range of switching point on falling pressure3.5...265 bar
Adjustable range of switching point on rising pressure20...300 bar
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
Auxiliary contacts operationSnap action
AWG gaugeAWG 24...AWG 14
Cable entry number1 tapped entry (Pg 13.5) forcable gland , cable outer diameter: 9...13 mm
Class of protection against electric shockClass I conforming to NF C 20-030 Class I conforming to IEC 536 Class I conforming to IEC 1140
Contacts materialSilver contacts
Contacts type and composition1 C/O
Controlled fluidHydraulic oil (0...160 °C)
Depth75 mm
Destruction pressure1350 bar
Device short nameXMLA
Electrical circuit typeControl circuit
Electrical connectionScrew-clamps terminals 1 x 0.2...2 x 2.5 mm²
Enclosure materialZinc alloy
Fluid connection typeG 1/4 (female) conforming to ISO 228
Height113 mm
IP degree of protectionIP66 conforming to EN/IEC 60529
Local displayWith
Materials in contact with fluidBrass FPM, FKM PTFE Steel
Maximum permissible accidental pressure675 bar
Maximum permissible pressure - per cycle375 bar
Mechanical durability3000000 cycles
Natural differential at high setting35 bar (+/- 6 bar)
Natural differential at low setting16.5 bar (+/- 3 bar)
Operating positionAny position
Operating rate<= 60 cyc/mn at > 0 °C
Pressure actuatorPiston
Pressure sensor size300 bar
Pressure sensor typeElectromechanical pressure sensor
Pressure switch type of operationDetection of 1 single threshold
Product certificationsBV CCC CSA GOST LROS (Lloyds register of shipping) RINA UL
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Product or component typeElectromechanical pressure sensor
Product specific application-
Product weight0.75 kg
Protective treatmentTC (standard version)
Range of productOsiSense XM
REAChReference not containing SVHC above the threshold
Repeat accuracy< 2 %
Resistance across terminals< 25 mOhm conforming to NF C 93-050 method A < 25 mOhm conforming to IEC 255-7 category 3
RoHS (date code: YYWW)Compliant - since 0928 -  Schneider Electric declaration of conformity
Scale typeFixed differential
SettingExternal
Shock resistance50 gn conforming to IEC 68-2-27
Short circuit protection10 A cartridge fuse type gG (gl)
StandardsCE EN 60947-5-1 EN/IEC 60947-5-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Terminal block type4 terminals
Vibration resistance4 gn (f = 30...500 Hz) conforming to IEC 68-2-6
Width35 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info