[In] rated current | 0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1 3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1 |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 500 V conforming to EN/IEC 60947-1 300 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-1 |
Adjustable range of switching point on falling pressure | 0.13...9.15 bar |
Adjustable range of switching point on rising pressure | 0.7...10 bar |
Ambient air temperature for operation | -25...70 °C |
Ambient air temperature for storage | -40...70 °C |
Auxiliary contacts operation | Snap action |
Class of protection against electric shock | Class I conforming to NF C 20-030 Class I conforming to IEC 536 Class I conforming to IEC 1140 |
Contacts material | Silver contacts |
Contacts type and composition | 1 C/O |
Controlled fluid | Hydraulic oil (0...160 °C) Fresh water (0...160 °C) Air (0...160 °C) |
Depth | 75 mm |
Destruction pressure | 45 bar |
Device short name | XMLB |
Electrical circuit type | Control circuit |
Electrical connection | 1 male connector DIN 43650 A 4 pins |
Enclosure material | Zinc alloy |
Fluid connection type | G 1/4 (female) conforming to ISO 228 |
Height | 113 mm |
IP degree of protection | IP65 conforming to EN/IEC 60529 |
Local display | With |
Materials in contact with fluid | Brass FPM, FKM |
Maximum permissible accidental pressure | 22.5 bar |
Maximum permissible pressure - per cycle | 12.5 bar |
Mechanical durability | 5000000 cycles |
Operating position | Any position |
Operating rate | <= 120 cyc/mn at > 0 °C |
Possible differential maximum at high setting | 7.5 bar |
Possible differential minimum at high setting | 0.85 bar (- 0.1 bar, + 0.15 bar) |
Possible differential minimum at low setting | 0.57 bar (+/- 0.05 bar) |
Pressure actuator | Diaphragm |
Pressure sensor size | 10 bar |
Pressure sensor type | Electromechanical pressure sensor |
Pressure switch type of operation | Regulation between 2 thresholds |
Product certifications | BV CCC CSA GOST LROS (Lloyds register of shipping) RINA UL |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product or component type | Electromechanical pressure sensor |
Product specific application | - |
Product weight | 0.735 kg |
Protective treatment | TC (standard version) |
Range of product | OsiSense XM |
REACh | Reference not containing SVHC above the threshold |
Repeat accuracy | < 2 % |
Resistance across terminals | < 25 mOhm conforming to NF C 93-050 method A < 25 mOhm conforming to IEC 255-7 category 3 |
RoHS (date code: YYWW) | Compliant - since 0928 - Schneider Electric declaration of conformity |
Scale type | Adjustable differential |
Setting | External |
Shock resistance | 50 gn conforming to IEC 68-2-27 |
Short circuit protection | 10 A cartridge fuse type gG (gl) |
Standards | CE EN/IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
Sustainable offer status | Green Premium product |
Terminal block type | 4 terminals |
Vibration resistance | 4 gn (f = 30...500 Hz) conforming to IEC 68-2-6 |
Width | 35 mm |