[In] rated current0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1 3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage300 V conforming to CSA C22.2 No 14 500 V conforming to EN/IEC 60947-1 300 V conforming to UL 508
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-1
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
AWG gaugeAWG 24...AWG 14
Cable entry number1 tapped entry (M20 x 1.5) forcable gland , cable outer diameter: 7...13 mm
Class of protection against electric shockClass I conforming to NF C 20-030 Class I conforming to IEC 536 Class I conforming to IEC 1140
Contacts type and composition2 C/O staggered, silver contacts 2 C/O snap action, silver contacts
Controlled fluidCorrosive fluid (0...160 °C)
Depth85 mm
Destruction pressure45 bar
Device short nameXMLD
Electrical circuit typeControl circuit
Electrical connectionScrew-clamps terminals 1 x 0.2...2 x 2.5 mm²
Enclosure materialZinc alloy
Fluid connection typeG 1/4 (female) conforming to ISO 228
Height113 mm
IP degree of protectionIP66 conforming to EN/IEC 60529
Local displayWithout
Materials in contact with fluidPTFE 316L stainless steel
Maximum permissible accidental pressure22.5 bar
Maximum permissible pressure - per cycle12.5 bar
Mechanical durability5000000 cycles
Natural differential at high setting0.6 bar
Natural differential at low setting0.45 bar
Operating positionAny position
Operating rate0...120 cyc/mn at > 0...70 °C
Pressure actuatorDiaphragm
Pressure sensor size10 bar
Pressure sensor typeElectromechanical pressure sensor
Pressure switch type of operationDetection of 2 single thresholds
Product certificationsCSA UL
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Product or component typeElectromechanical pressure sensor
Product specific applicationDual stage
Product weight0.705 kg
Protective treatmentTC (standard version)
Range of productOsiSense XM
REAChReference not containing SVHC above the threshold
Repeat accuracy< 2 %
Resistance across terminals< 25 mOhm conforming to NF C 93-050 method A < 25 mOhm conforming to IEC 255-7 category 3
RoHS (date code: YYWW)Compliant - since 0928 -  Schneider Electric declaration of conformity
Scale typeFixed differential
SettingExternal
Shock resistance50 gn conforming to IEC 68-2-27
Short circuit protection10 A cartridge fuse type gG (gl)
Spread between 2 stages0.68...5.8 bar
StandardsCE EN/IEC 60947-5-1 UL 508 CSA C22.2 No 14
Sustainable offer statusGreen Premium product
Terminal block type8 terminals
Vibration resistance4 gn (f = 30...500 Hz) conforming to IEC 68-2-6
Width46 mm